Goodman Mfg VC8 instruction manual Operational Checks & Safety Circuit Description

Models: VC8

1 48
Download 48 pages 50.02 Kb
Page 35
Image 35
OPERATIONAL CHECKS

OPERATIONAL CHECKS & SAFETY CIRCUIT DESCRIPTION

Gas valve opens at end of igniter warm up period, delivering gas to burners and establishing flame.

Integrated control module monitors flame presence. Gas valve will remain open only if flame is detected.

If the thermostat call is for low heat, gas valve and induced draft blower will continue on low stage. If the call is for high heat, the gas valve and induced draft blower will change to high stage.

Circulator blower is energized on heat speed following a thirty (30) second blower on delay. The circulator blower requires thirty seconds to ramp up to full speed. Electronic air cleaner terminal is energized with circulator blower.

Furnace is now operating on the specified stage called for by the two-stage thermostat.

Furnace runs, integrated control module monitors safety circuits continuously.

If the two-stage thermostat changes the call from low heat to high heat, the integrated control module will immediately switch the induced draft blower, gas valve, and circulator blower to their high stage settings.

If the two-stage thermostat changes the call from high heat to low heat, the control will immediately switch the induced draft blower and gas valve to their low stage settings. The circulator blower will remain on high heating speed for thirty (30) seconds before switching to the low heat circulating speed.

R and W1 (or R and W1/W2) thermostat contacts open, completing the call for heat.

Gas valve closes, extinguishing flame.

Induced draft blower is de-energized following a fifteen second post purge. Humidifier terminals are de-energized.

Circulator blower continues running for the selected heat off delay period (90, 120, 150 or 180 seconds). The speed run during this period depends on the last heat call provided by the thermostat.

If the last call for heat was a call for low heat, the air circulator motor will run on low heat speed for the duration of the heat off delay period (90, 120, 150 or 180 seconds). If the last call for heat was a call for high heat, the air circulating motor will run on the high heating speed for thirty (30) seconds and then switch to the low heating speed for the balance of the heat off delay period (60, 90, 120 or 150 seconds).

Circulator blower and electronic air cleaner terminal is de-energized.

Circulator blower ramps down to OFF during the 30 seconds following the heat off delay period.

Furnace awaits next call from thermostat.

COOLING MODE

The normal operational sequence in cooling mode is as fol- lows:

R and Y1/G or Y2/G thermostat contacts close, initiating a call for cool.

Integrated control module performs safety circuit checks.

Outdoor fan and compressor are energized to their appropriate speed.

Circulator blower is energized on the appropriate cool speed at the level and time determined by the selected ramping profile. Electronic air cleaner terminal is energized with circulator blower.

Furnace circulator blower and outdoor cooling unit run their appropriate speeds, integrated control module monitors safety circuits continuously.

R and Y1/G or Y2/G thermostat contacts open, completing the call for cool.

Outdoor fan and compressor are de-energized.

Circulator blower continues running during a cool off delay period. The OFF delay time and airflow level are determined by the selected ramping profile.

Electronic air cleaner terminal and circulator blower are de-energized.

Furnace awaits next call from thermostat.

FAN ONLY MODE

The normal operational sequence in fan only mode is as fol- lows:

R and G thermostat contacts close, initiating a call for fan.

Integrated control module performs safety circuit checks.

Circulator blower is energized on continuous fan speed (30% of the furnace’s maximum airflow capability) following a five (5) second delay. Electronic air cleaner terminal is energized.

Circulator blower runs, integrated control module monitors safety circuits continuously.

R and G thermostat contacts open, completing the call for fan.

Circulator blower is de-energized. Electronic air cleaner terminal is de-energized.

Furnace awaits next call from thermostat.

OPERATIONAL CHECKS

The burner flames should be inspected with the burner com- partment door installed. Flames should be stable, quiet, soft, and blue (dust may cause orange tips but they must not be yellow). Flames should extend directly outward from the burn- ers without curling, floating, or lifting off. Flames must not impinge on the sides of the heat exchanger firing tubes.

35

Page 35
Image 35
Goodman Mfg VC8 instruction manual Operational Checks & Safety Circuit Description