2.Check the Blower Rotation
Open the blower access door and run the blower momentarily to determine the rotation. Arrows are placed on the blower scroll to indicate the proper direction or reference the example shown.
|
|
| n |
|
|
| io |
|
|
| t |
|
| a | |
R | o | t |
|
|
| ||
|
|
|
Blower
Housing
Blower Rotation
5.Air Volume Measurement and Check
Measure the unit’s air volume (cfm) and compare it with it’s rated air volume. If the measured air volume is off, adjust the fan’s RPM by changing/adjusting the drive.
Note
The most accurate way to measure the air volume is by using a pitot traverse method downstream of the
Note
To reverse the rotation on three phase units, disconnect and
Note
To reverse the rotation on single phase units, disconnect and
Important
If the blower is rotating in the wrong direction, the unit will move some air, but will not perform as designed. Be sure to perform a visual inspection to guarantee the correct blower rotation.
3. Check for Vibration
Check for unusual noise, vibration or overheating of the bearings. Reference the Troubleshooting section for corrective actions.
Important
Excessive vibration may be experienced during the initial
Important
Generally, fan vibration and noise is transmitted to other parts of the building by the ductwork. To minimize this undesirable effect, the use of heavy canvas duct connectors is recommended.
4. Motor Check
Measure the motor’s voltage, amps and RPM. Compare to the specifications. Motor amps can be reduced by lowering the motor RPM or increasing system static pressure.
Important
Additional starters and overloads may be provided in the
blower. Other methods can be used but should be proven and accurate.
Important
Changing the air volume can significantly increase the motor’s amps. If the air volume is changed, the motor’s amps must be checked to prevent overloading the motor.
Note
To ensure accuracy, the dampers are to be open when measuring the air volume.
6. Set-Up Optional Components
Adjust the settings on the optional components. See the Control Center Layout in the Reference section for location of optional components.
• Building Freeze Protection
Typical setting: 5 minutes; 45ºF (7ºC)
• Dirty Filter Gauge
Typical setting: Settings vary greatly for each unit. (see Reference section for adjusting information)
10 DGX Industrial Space Heating
®