Heater Does Not Operate

Troubleshooting

Heater Does Not Operate

Does not attempt to light (No visible spark)

24 VAC between

No

 

terminals W1 and X?

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

115 VAC between

No

 

terminals 102 and 101?

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

115 VAC between

No

 

terminals 103 and 101?

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

115 VAC between

No

 

terminals 104 and 101?

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

115 VAC between

No

 

terminals 106 and 101?

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

Continuity between

No

 

terminals 107 and 108?

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat Switch (S4) Off

(Turn Heat Switch (S4) On)

Heat Switch Not Wired

(Wire Heat Switch (S4))

Primary Fuses Blown

(Replace Fuses)

Main Transformer (TR4) Defective

(Replace Transformer)

(Optional) Inlet Air Sensor (TS4) Holding

(Adjust TS4 setting. Reference Blower Start-Up – Step #6)

Heat Relay (RH) Defective

(Replace Heat Relay (RH))

The power light on the flame safeguard should

blink approximately every 5 seconds as it

performs a self-diagnostics check.

High Limit (HLC1) Tripped

(Reset/Replace High Limit (HLC1)) (Check on cause of control loss)

(Optional) High/Low Gas Pressure Switch(es)

(PS3 and PS4) Tripped

(Correct gas pressure and reset)

(Reference Direct Gas Start-Up – Steps #2 and #3)

Airflow Switch (PS2) Holding for Proper Airflow

(Correct airflow across burner)

(Reference Direct Gas Start-Up – Step #4a or 4b)

At this time the heater should attempt to light.

(The pilot light on the flame safeguard should illuminate).

®

DGX Industrial Space Heating 21

Page 21