Greenheck Fan Part #470655 manual Installation of Diffuser and Remote Panel TSCP, Install Diffuser

Models: Part #470655

1 32
Download 32 pages 30.25 Kb
Page 6
Image 6
Installation of Diffuser and Remote Panel (TSCP)

Installation of Diffuser and Remote Panel (TSCP)

NOTE

The location of the discharge diffuser and the TSCP Space Heat Remote Panel are critical for optimum performance of the Greenheat™ System.

1. Install Diffuser

Using self-tapping screws, attach diffuser to the ductwork or unit. Be sure to maintain the recommended floor to diffuser height. Refer to the chart for the recommended diffuser height.

Airflow

 

Diffuser Height (feet)

(cfm)

Minimum

 

Recommended

Maximum

 

 

 

 

 

4000

15

 

20

25

 

 

 

 

 

6000

15

 

20

25

 

 

 

 

 

8000

20

 

20-25

30

 

 

 

 

 

10000

20

 

25-30

35

 

 

 

 

 

13000 -

25

 

30-35

40

 

20000

 

 

 

 

 

 

 

 

 

 

2. Install TSCP

When installing the TSCP Space Heat Remote Panel, the location is critical to performance of the Greenheat™ System. The TSCP should be installed five to six feet above the floor. It is recommended that the TSCP be installed on an outside wall, in the space, and close to any source of infiltration such as dock doors. DO NOT install the TSCP in the blast area of the heater or near any other source of heat.

Important

DO NOT install the TSCP in the blast area of the space heater or near any other source of heat.

Recommended

TSCP Location

Blast Area

Indoor Mounted

Unit

TSCP Location

h

Thru-Wall Diffuser Height

Rooftop

Unit

h

Rooftop Diffuser Height