4. Pipe the Optional Vent Line
If an optional vent line is located between the safety shutoff valves it must be piped to the outdoors.
warning
Reference the National Fuel Gas Code for additional vent line requirements.
| Vent Line Solenoid |
| to outdoors |
| LineVent |
to burner | from supply |
Safety
Optional Vent Line
5. Test the System for Leaks
Check both the supply lines and the factory piping for leaks. Apply a soap and water solution to all piping and watch for bubbling which indicates a leak.
warning
NEVER test for a gas leak with an open flame.
Note
The factory piping has been checked for leaks, but should be rechecked due to shipping and installation.
Start-Up - Blower
Refer to the
Pre Start-Up Check
Rotate the fan wheel by hand and make sure no parts are rubbing. Check the
is provided in the Maintenance,
warning
Disconnect and
SPECIAL TOOLS REQUIRED
•Voltage Meter (with wire probes)
•Amperage Meter
•Micro Amp Meter
•Tachometer
•Thermometer
•Incline manometer or equivalent
Warning
Check the housing, blower, and ductwork for any foreign objects before running the blower.
1. Check the Voltage
Before starting the unit, compare the supplied voltage, hertz, and phase with the unit and motor’s nameplate information.
VOLTS |
| HZ |
| PH |
SUP HP
MCA |
| MOP |
Unit’s Total MCA
Electrical Nameplate
®
DGX Industrial Space Heating 9