Start-Up Direct Gas continued

Start-Up Direct Gas continued

important

Setting the maximum firing rate during mild weather conditions may cause the high limit to trip out during extreme conditions requiring manual resetting.

note

The minimum setting for the maximum firing rate may be higher than required. This is acceptable, the burner will still modulate as needed.

note

Gas trains are equipped with either a separate regulator and modulating valve or with a combined modulating regulator.

note

Clockwise rotation increases the temperature rise, counterclockwise rotation decreases the temperature rise.

Regulators and Modulating Valves

Remove cap to access

 

Remove one wire to

maximum firing rate

 

send the unit to the

 

adjustment

 

minimum firing rate

Minimum firing rate adjustment

Separate Regulator and Modulating Valves

Minimum firing

 

Maximum firing

 

rate adjustment

 

rate adjustment

7. Set the Minimum Firing Rate

Disconnect and isolate one of the wires running to the modulating valve to send the unit to its minimum firing rate. Set the minimum firing rate by adjusting the needle valve as shown in the diagrams on this page.

After setting the minimum firing rate, shut off the pilot to ensure that the flame safeguard can still read the main flame signal. Reconnect the wire to the modulating valve and open the pilot shut-off valve.

important

The proper setting for the minimum firing rate results in a small ribbon of continuous flame across the entire burner.

important

Do not allow the disconnected wire to come in contact with a potential ground. Damage to the amplifier or transformer could result.

note

On units with a 42 inch or greater burner, the flame safe guard will automatically shut off the pilot

10 seconds after the burner has been ignited.

note

Gas trains are equipped with either separate regulators and modulating valves or with a combined modulating regulator.

note

Adjusting the maximum and minimum fire requires the inlet air sensor to be set higher than the outdoor air temperature in order to start the burner. Once high and low fire have been set, the inlet air sensor should be set to the desired temperature.

8. Set Daytime Temperature

Set the daytime temperature setting to the desired daytime space temperature, the daytime temperature setting is located inside the TSCP Space Heat remote panel which should be mounted in the space.

Transformer

Side

Top

View

View

 

Remove one wire to send the unit to the minimum firing rate

Combined Modulating Regulator

7-Day Timer

 

Terminal

(optional)

 

Strip

 

 

 

 

 

 

Night

 

Day

Temperature

 

 

Temperature

Setting

 

 

Setting

(optional)

 

 

 

 

 

 

 

 

 

TSCP Space Heat Remote Panel Controls

®

DGX Industrial Space Heating 13

Page 13
Image 13
Greenheck Fan Part #470655 Start-UpDirect Gas continued, Regulators and Modulating Valves, Set the Minimum Firing Rate