Section 5

ENGINE DC CONTROL SYSTEM

CIRCUIT CONDITION- SHUTDOWN:

Setting the START-STOP SWITCH (SW1) or the REMOTE PANEL START-STOP SWITCH to its "STOP" position, connects the Wire 18 circuit to ground. ENGINE CONTROL circuit board action de- energizes DC output to Terminal 9,10, & 11 (Wire 14). The FUEL PUMP (FP), FUEL SOLENOID (FS) and HOURMETER (HM) are de-energized by the loss of DC to Wire 14. Fuel flow terminates and the engine shuts down.

Page 22

Page 24
Image 24
Guardian Technologies 4270 manual Circuit CONDITION- Shutdown