Installation Procedure
ELECTRICAL WIRING
Connect wiring to the terminals
A.For solid core wiring (or
(1)Cut the wire end with a wire cutter or
(2)Using a screwdriver, remove the terminal screw(s) on the terminal board.
(3)Using pliers, bend the solid wire to form a loop suitable for the terminal screw.
(4)Shape the loop wire properly, place it on the terminal board and tighthen securely with the terminal screw using a screwdriver.
B.For strand wiring
(1)Cut the wire end with a wire cutter or
(2)Using a screwdriver, remove the terminal screw(s) on the terminal board.
(3)Using a round terminal fastener or pliers, securely clamp a round terminal to each stripped wire end.
(4)Position the round terminal wire, and replace and tighten the terminal screw using a screwdriver.
Strip 15/16"(25mm)
A. Solid wire
Loop
Insulation
Strip 3/8"(10mm)
B. Strand wire | Screw with |
|
| special washer |
|
Round | Round |
|
terminal |
| |
terminal |
| |
|
| |
Wire | Terminal | Wire |
board |
|
Screw with special washer
Round terminal
Fix connection cord and power cable at the cord clamp | Insulation tube | |
Cord clamp | ||
After passing the connection cord and power cable through the insulation tube, | ||
| ||
fasten it with the cord clamp. |
| |
Use |
|
Electrical requirement
Select wire sizes and circuit protection from table below. (This table shows 20m length wires with less than 2% voltage drop).
Item |
| Circuit | breaker | Power source | Earth leakage breaker | ||
Phase |
|
| wire size |
|
| ||
| Switch breaker | Overcurrent protector | Switch | Leak | |||
Model | (minimum) | ||||||
| (A) | rated capacity (A) | breaker(A) | current(mA) | |||
| (mm2) | ||||||
AC28ES1ERA | 1 | 40 | 30 | 6.0 | 40 | 30 | |
AC36ES1ERA | |||||||
|
|
|
|
|
| ||
AC48FS1ERA | 1 | 30 | 20 | 4.0 | 10 | 30 | |
AC60FS1ERA | |||||||
|
|
|
|
|
|
CAUTION
Match the terminal block numbers and connection cord colors with those of the outdoor unit. Erroneous wiring may cause burning the electric parts.
Connect the connection cords firmly to the terminal block. Imperfect installation may cause a fire.
Always fasten the outside covering of the connection cord with the cord clamp. If the insulator is chafed, electric leakage may occur.
Always connect the ground wire.
Connect indoor unit and outdoor unit
(1)Remove the cord clamp.
(2)Process the end of the connection cords to the dimensions shown in wiring diagram.
(3)Connect the end of the connection cord fully into the terminal block.
(4)Fasten the connection cord with a cord clamp.
(5)Fasten the end of the connection cord with the screw.