Venting

3 ft.

to combustibles

Fig. 8

 

 

 

 

3 ft.

 

to combustibles

#1 Preferred method

This method provides excellent venting for normal operation and allows the stove to be in- stalled closest to the wall. Two inches from the wall is safe; however, four inches allows better access to remove the rear panel. The vertical portion of the vent should be three to five feet high. This vertical section will help provide natural draft in the event of a power failure. Note: Do not place joints within wall pass-throughs.

3 ft.

to combustibles

 

 

 

 

Fig. 9

 

3 ft.

to combustibles

#2 Preferred method

This method also provides excellent venting for normal operation but requires the stove to be installed farther from the wall. The vertical portion of the vent should be three to five feet high and at least three inches from a combustible wall. This vertical section will provide natural draft in the event of a power failure.

If the stove is installed below grade be sure the vent termination is at least 18" above grade. The outlet must also be 1 foot from the house/building.

Note: Do not place joints within wall pass- throughs.

CAUTION

Keep combustible materials (such as grass, leaves, etc.) at least 3 feet away from the flue outlet on the outside of the building.

12" min. wall to outlet

36" min clearance to any combustible material

P61A Pellet Stove 11

Page 11
Image 11
Harman Stove Company P61A manual #1 Preferred method, #2 Preferred method