Over Heat Safety Zone

Over Heat Safety Zone

OverHeat Safety Zone (Dump Zone): STRONGLY RECOMMENDED in all installations.

When the pellet boiler is operating at High burn, and all demand from the heating system stops, the control will reduce the feed rate and shut down completely as necessary. This may take several minutes, and the remain- ing heat may cause the water temperature to continue to rise. If the temperature gets too high, the OVERHEAT SAFETY ZONE light on the control (see page 23) will illuminate, and the DARK BLUE circuit in the junction box is energized(see wiring diagram). This circuit will flow 120V to operate a circulator pump installed to flow to the overheat dump zone established in the original installation plan. If opening a zone valve is the chosen method of dumping the excess heat, a voltage reduction relay will most likely be needed. If the water temperature continues to rise to the risk of boiling point, the feed system will stop and the boiler will shut-down. A manual reset will then be required to operate the boiler. Without a dump zone in place, the excess temperature will build pressure to the point of opening the relief valve, or with the atmospheric conversion it will allow the water to boil and over-flow the atmospheric tank. Both scenarios may create water damage and/or slip hazard.

The boiling temperature of water varies at different altitudes and atmospheric pressures. Therefore, at eleva- tions above 3000 feet, and when using the atmospheric conversion, circuit board dipswitch #6 must be in the “ON” position.

Power Failure / Heat Dissipation Loop

EXAMPLE OF PIPING IN ACCORDANCE

WITH (CAN/CSA-B366.1)

A POWER FAILURE HEAT DISSIPATION LOOP

BALANCING

 

SYSTEM SUPPLY

VALVE

 

 

 

 

 

 

 

 

 

UNION

POWER FAILURE SYSTEM SUPPLY 3/4"

*TEMPERATURE/PRESSURE GAUGE

*AQUASTAT WELL

*PRESSURE RELIEF VALVE

PIPE TO WITHIN 6" OF THE FLOOR OR A FLOOR DRAIN

UNION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MINIMUM OF 72" OF 3/4"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(HIGH TEMPERATURE) BASEBOARD HEAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FINNED BASEBOARD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BASEBOARD MUST BE AT LEAST

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24" HIGHER THAN BOILER FOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PROPER GRAVITY FLOW

120VAC,NORMALLY OPEN,FULL FLOW, SOLENOID VALVE or EQUIVALENT

THE SOLENOID SHOULD BE POWERED BY THE SAME CIRCUIT AS THE BOILER

POWER FAILURE SYSTEM RETURN 3/4"

SHUT-OFF VALVE

 

 

 

 

SHUT-OFF VALVE

SYSTEM RETURN

 

 

NOTE: ALWAYS REFER TO THE INDIVIDUAL COMPONENTS

 

RECOMMENDED INSTALLATION INSTRUCTIONS FOR THE PROPER

* ITEMS SUPPLIED

MOUNTING POSITION AND LOCATION WITHIN THE PIPING SYSTEM.