A. PipeClearancestoCombustibles

Vent clearances are per vent manufacturer’s specica-
tions. MUST be Listed B-Vent pipe.
WARNING! Risk of Fire! Maintain air space clearance to
vent. DO NOT pack insulation or other combustibles:
• Between ceiling restops
• Between wall shield restops
• Around vent system
Failure to keep insulation or other material away from
vent pipe may cause over heating and re.
8 VentClearancesandFraming 

B. WallandCeilingPenetrationFraming

For a wall or ceiling penetration consult B-vent pipe manu-
facturer’s instructions to provide adequate clearances. Use
same size framing materials as those used in the wall or
ceiling construction. Firestop spacers must be used in wall
and ceiling penetrations per the B-Vent pipe manufacturer’s
specications and national, regional and local codes.
Note: MUST terminate vertically.

C. VerticalPenetrationFraming

WARNING! Fire Risk. DO NOT allow loose materials or
insulation to touch vent. Hearth & Home Technologies
Inc. requires the use of an attic shield.
The National Fuel Gas Code ANSI Z223.1 and NFPA 54
requires an attic shield constructed of 26 gauge minimum
metal that extends at least 2 in. (51 mm) above insulation.
Attic shields must meet specied clearance and be se-
cured in place.
Use B-vent manufacturer’s restops to provide adequate
clearances.