6 Gas Information

A. Gas Pressure Requirements

B. Gas Connection

Pressure requirements for Heat & Glo gas fireplaces are shown in Table 1 below.

Two taps are provided on the outlet side of the gas control for a test gauge connection to measure the inlet and outlet pressures. These inlet and outlet pressure taps can be ac- cessed through the internal valve access panels as shown in Section 11: Maintaining and Servicing the Fireplace.

The fireplace and its individual shut-off valve must be dis- connected from the gas supply piping system during any pressure testing of the system at test pressures in excess of 60 mbar.

If the fireplace must be isolated from the gas supply piping system by closing an individual shut-off valve, it must be of the handle-less type.

Note: Have the gas supply line installed in accordance with local building codes by a qualified installer approved and/or licensed as required by the locality.

Note: Before the first firing of the fireplace, the gas supply line should be purged of any trapped air.

Note: Consult local building regulations to properly size the gas supply line leading to the (Rp 1/2 in.) hook-up at the unit.

Incoming gas line should be piped into the valve compart- ment and connected to the ISO 7-Rp 1/2 (BSP Rp 1/2) threaded gas inlet connection on the manual shutoff valve.

Note: Gas line MUST be run from right side of fireplace.

WARNING

Fire Risk

Explosion Risk

High pressure will damage valve.

Disconnect gas supply piping BEFORE pressure testing gas line at test pressures above 60 mbar.

Close the manual shutoff valve BEFORE pressure testing gas line at test pressures equal to or less than 60 mbar.

Table 1

WARNING

CHECK FOR GAS LEAKS

Fire Risk

Explosion Risk

Asphyxiation Risk

Check all fittings and connections.

Do not use open flame.

After the gas line installation is complete, all connections must be tightened and checked for leaks with a commercially available, non-corrosive leak check solution. Be sure to rinse off all leak check solution following testing.

Fittings and connections may have loosened during shipping and handling.

 

Natural Gas

Propane

Butane

Natural Gas

 

(G20)

(G31)

(G30)

(G25)

Inlet Pressure

20mbar

37 or 50mbar

30 or 50mbar

25mbar

 

 

 

 

 

Manifold Pressure

4-8.7 mbar

24mbar

24mbar

8.7mbar

 

 

 

 

 

 

 

 

 

Gas Rate

1.68

m3 h

.62

m3 h

.42

m3 h

1.68

m3 h

 

/

/

/

/

Max.Input (NETCV)

16.5 kW

15.0 kW

13.7kW

14.0 kW

 

 

 

 

 

Burner Injector

DMS 25

DMS 44

DMS 46

DMS 25

 

 

 

 

 

Pilot Injector

51

30

30

51

 

 

 

 

 

 

 

 

 

Heat & Glo Lifestyle Collection • Dakota 42-CE4036-915 Rev I • 11/07