6 Complete the Enclosure
A. Chimney Termination
Chimney Termination Requirements (See Figures 6.1 and 6.2)
•Must have a cap approved and listed for this fireplace system
•Must not be located where it will become plugged by snow or other material
•Must terminate at least 3 ft (914 mm) above the roof and at least 2 ft (610 mm) above any portion of the roof within 10 ft (3.05 m)
•Must be located away from trees or other structures
Slanted Roofs
Chimney must |
|
| Chimney must extend 2 ft (.6 m) |
|
|
| above any portion of the roof |
| |
extend 3 ft (.9 m) |
|
|
| |
|
| within 10 ft (3 m) of the chimney |
| |
above the roof |
|
|
| |
|
|
|
|
|
|
|
|
|
|
Flat Roofs
Chimney must extend 2 ft (.6 m) above any portion of the roof within 10 ft (3 m) of the chimney
Chimney must extend 3 ft (.9 m) above the roof
Figure 6.1 Termination Requirements
| Gas, Wood or Fuel |
| |
| Oil Termination |
| |
|
|
| 20 in. |
|
|
| (508 mm) |
| 18 in. |
| (minimum) to |
|
| Perpendicular | |
| (457 mm) |
| Wall |
|
| A | (gas only) |
|
|
| |
Gas |
|
|
|
Termination |
|
| |
Gas Termination | Wood & Fuel Oil Terminatio | ||
A | 6 in. (152 mm) |
| 20 in. (508 mm) |
Figure 6.2 | Multiple Chimneys |
|
Mark the Exit Point of the Roof
Locate the point where the chimney will exit the roof by plumbing down to the center of the chimney. Drive a nail up through the roof to mark the center. See Figure 6.3.
Cut Out the Hole in the Roof
Measure to either side of the nail and mark the
WARNING
Fire Risk
•Must maintain 2 in. (51 mm) air clearance to insulation and other combustible materials.
Assemble the Chimney Sections Through the Roof
Continue to add chimney sections through the roof opening, maintaining at least a 2 in. (51 mm) air space to combustible materials.
Install the Roof Flashing |
|
If a roof flashing is to be used, install the roof flashing appropriate to the |
|
roof pitch and install a round termination cap and storm collar following the |
|
instructions shipped with the cap. | Figure 6.3 Ceiling/Attic Construction |