Heat & Glo • SL-350TRS-CE-D • 2033-900 Rev. N • 10/07
24
For Vertical Runs - The flue system must be
supported every 2.4 m above the heater flue outlet by
wall brackets.
To install support brackets for vertical runs:
• Attach wall brackets to the flue pipe and secure the
wall bracket to the framing members with nails or
screws.
Figure 29. Installing Support Brackets
WALL BRACKET
WALL STUD
8 FT.
(2.4 m)
FLUE
OUTLET
1 INCH MIN.
(25 mm)
4. Install FirestopsFor Horizontal Runs - Firestops are REQUIRED on
both sides of a combustible wall through which the
flue passes.
To install firestops (heat shield) for horizontal runs that
pass through either interior or exterior walls:
• Cut a 10-inch by 12-inch (254 mm X 305 mm) hole
through the wall.
• Position the firestops on both sides of the hole pre-
viously cut and secure the firestops with nails or
screws.
• The pipe opening of the firestops MUST BE placed
towards the bottom of the firestop.
• Continue the flue run through the firestop.