25
Heat & Glo • SL-350TRSI-AUE • 2089-902 Rev. B • 6/06
Figure 34.
1.6 FINISHING
The minimum clearance to combustibles are 0 from
the sides, floor, back and top (these clearances are
defined by the standoffs). The minimum distance to the
perpendicular side wall extending past the appliance
front is 2-inches (51mm). Clearance to a mantelpiece
is shown in Figure 34.
IF JOINTS BETWEEN THE FINISHED WALLS AND
THE FIREPLACE SURROUND (TOP AND SIDES)
ARE SEALED, A 300° F (149°C). MINIMUM SEAL-
ANT MATERIAL MUST BE USED. THESE JOINTS
ARE NOT REQUIRED TO BE SEALED. ONLY NON-
COMBUSTIBLE MATERIAL (USING 300° F . (149°C)
MINIMUM ADHESIVE, IF NEEDED) CAN BE AP-
PLIED AS FACING TO THE FIREPLACE SUR-
ROUND. SEE FIGURE 34.
½ in.
(12.7mm)
0
SIDE SEAL
JOINT
TOP SEAL
JOINT
CEILING
31
(787)
12
(305)
11
(279)
10
(254)
9
(229)
8
(203)
7
(178)
6
(152)
5
(127)
4
(102)
3
(76)
2
(51)
TOP FRONT EDGE
OF FIREPLACE
NON-COMBUSTIBLE
STRIP
10(254)
8(203)
12(305)
11(279 )
9(229)
7(178)
6(152)
5(127)
4(102)
3(76)
2(51)
Note: Dimensions in
inches (mm).