1. Top Vent - Horizontal Termination - (continued)

Two Elbows

Note: There MUST be a 25% reduction in total H when using flex vent except when using the simple up and out installation (see Figure 7.3).

V1 Minimum

H1 + H2 Maximum

1 ft.**

305 mm

1 ft.

305 mm

 

 

 

 

2 ft.**

610 mm

2 ft.

610 mm

 

 

 

 

3 ft.**

915 mm

4 ft.

1.2 m

4 ft.

1.2 m

6 ft.

1.8 m

5 ft.

1.5 m

14 ft.

4.3 m

 

 

 

 

H + H1 Max. =14 ft. (4.3 m)

V + H + H1 Max. = 40 ft. (12.2 m)

See Warning Below**

H2

INSTALLED

HORIZONTALLY

WARNING**

Fire Risk.

When using SLP-HRC-SS and SLP-HRC-ZC-SS termination caps on top vented fireplaces, a two foot minimum vertical vent section is required before

installing first elbow.

When using DVP-TB1 termination cap on top vented fireplaces, a three foot minimum vertical vent section is required before installing first elbow.

When using any other cap, a section of vertical pipe (12 inches minimum) MUST be installed prior to attaching a 90° elbow.

V1 H1

Figure 7.5

Heat & Glo • ST-550TM-IPI2142-900 Rev. B • 11/08