1. Top Vent - Horizontal Termination - (continued)

Three Elbows

Note: There MUST be a 25% reduction in total H when using flex vent except when using the simple up and out installation (see Figure 7.3).

V1 Minimum

H1 + H2 Maximum

V2

V1 + V2 Min.

1 ft.**

305 mm

1 ft.

305 mm

*

*

 

 

 

 

 

 

2 ft.**

610 mm

2 ft.

610 mm

*

*

 

 

 

 

 

 

3 ft.**

915 mm

4 ft.

1.2 m

*

*

4 ft.

1.2 m

6 ft.

1.8 m

*

*

5 ft.

1.5 m

14 ft.

4.3 m

*

*

 

 

 

 

 

 

H1 + H2 Max. =14 ft. (4.3 m)

V1 + V2 + H1 + H2 Max. = 40 ft. (12.2 m) *No specific restrictions on this value

EXCEPT V1 + V2 + H cannot exceed 40 ft. (12.2 m)

See Warning Below**

Note: A section of vertical pipe (12 inches minimum)

MUST be installed prior to attaching a 90° elbow.

H2

V2

V1

H1

WARNING**

Fire Risk.

When using SLP-HRC-SS and SLP-HRC-ZC-SS termination caps on top vented fireplaces, a two foot minimum vertical vent section is required before installing first elbow.

When using DVP-TB1 termination cap on top vented fireplaces, a three foot minimum vertical vent section is required before installing first elbow.

When using any other cap, a section of vertical pipe (12 inches minimum) MUST be installed prior to attaching a 90° elbow.

Figure 7.6

28

Heat & Glo • ST-550TM-IPI2142-900 Rev. B • 11/08