Heat & Glo LifeStyle BE-41 3Installing the Fireplace, Locating the Fireplace, Horizontal Sections

Models: BE-41

1 31
Download 31 pages 27.93 Kb
Page 9
Image 9
3Installing the Fireplace

3Installing the Fireplace

Step 1. Locating the Fireplace

The diagram below shows space and clearance require- ments for locating a fireplace within a room.

A

 

B

C

D

E

42”

22”

36”

51”

72”

Figure 2.

Fireplace Dimensions, Locations,

 

 

and Space Requirements

 

Clearance Requirements

The top, back, and sides of the fireplace are defined by stand-offs. The minimum clearance to a perpendicular wall extending past the face of the fireplace is one inch (25 mm). The back of the fireplace may be recessed 21 1/2 inches (546 mm) into combustible construction.

Minimum Clearances

from the Fireplace to Combustible Materials

 

Inches

mm

Glass Front

........................ 36

914

Floor

0

0

Rear

1/2

13

Sides

1/2

13

Top

3 1/2

89

Ceiling*

31

787

*The clearance to the ceiling is measured from the top of the unit, excluding the standoffs (see Figure 35).

The distance from the unit to combustible construction is to be measured from the unit outer wrap surface to the combustible construction, NOT from the screw heads that secure the unit together.

Minimum Clearances

from the Vent Pipe to Combustible Materials

 

Inches

mm

Vertical Sections

1

25

Horizontal Sections

 

 

Top

3

75

Bottom

1

25

Sides

1

25

At Wall Firestops

 

 

Top

2 1/2

63.7

Bottom

1/2

13

Sides

1

25

For minimum clearances, see the direct vent termination clearance diagrams on pages 22 and 23 in this manual.

9

Page 9
Image 9
Heat & Glo LifeStyle BE-41 manual 3Installing the Fireplace, Locating the Fireplace, Horizontal Sections, At Wall Firestops