4. SIDEWALLS/SURROUNDS.

BW36 SERIES WOODBURNING FIREPLACE

No one builds a better fire

4. SIDEWALLS/SURROUNDS.

Adjacent combustible side walls must be located a minimum of 12" from the fireplace opening. See Figure 7. If you are using a decorative surround constructed of combustible material, it may be located within the shaded area defined in Figure 7. Short stub walls are also acceptable if they are contained within the shaded area.

BRICK

FLUSH FRONT

 

FRONT

4"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12"

 

143/8"

A

 

93/4"

 

 

50°

B

 

 

 

 

39°

12"

 

 

 

 

 

 

 

 

 

12"

 

12"

 

MIN.

 

 

 

 

 

CAT. #

A

B

 

TOP OF

335/8"

 

 

385/8"

 

FIREPLACE

BW36

36"

 

 

 

OPENING

 

BW36C

36"

385/8"

 

 

 

Figure 7

Sidewalls/Surrounds

5. MANTEL.

A combustible mantel may be positioned no lower than 12” above the top of the firebox opening. The combustible mantel may have a maximum depth of 12”. Combustible trim materials, projecting no more than 1 1/2” from the face of the fireplace, can be placed no closer than 6” from the top and side of the

firebox opening. (See the shaded areas on each side of the firebox, as defined in Figure 7). Combustible trim must not cover the black metal sur- faces of the fireplace. This mantel clearance is in accordance with Section 7-3.3.3 of ANSI/NFPA 211.

E. CHIMNEY REQUIREMENTS

When planning your fireplace location, the chimney construction and necessary clearances must be considered. The fireplace system and chimney components have been tested to provide the following flexibility in construc- tion. The following figures are the minimum distances from the base of the unit.

Minimum overall straight height

14.5 ft.

Minimum height with Offset/Return

14.5 ft.

Maximum height

90 ft.

Maximum chimney length between an Offset/Return

12 ft.

Maximum distance between Chimney Stabilizers

35 ft.

Double Offset/Return minimum height

20 ft.

Maximum unsupported chimney length between Offset/Return

6 ft.

Maximum straight unsupported chimney height above firebox

25 ft.

1. USING OFFSETS AND RETURNS.

To bypass any overhead obstructions, the chimney may be offset using a 15° offset/return (SL315) or a 30° offset/return (SL330). Perform the following steps to determine the correct chimney component combi- nation for your particular installation.

An offset and return may be attached together or a chimney section(s) may be used between an offset and return. However, the distance between two

elbows must never exceed 12 feet in total length.