Heat & Glo LifeStyle EVEREST Wiring the Fireplace, Optional Accessories, Appliance Requirements

Models: EVEREST

1 27
Download 27 pages 12.36 Kb
Page 23
Image 23
Step 8. Wiring the Fireplace

 

 

 

 

 

 

INTERMITTENT

PLUG-IN

 

 

 

IGNITION MODULE

 

PILOT

 

 

 

3 VAC

 

IGNITOR

3V TRANSFORMER

 

 

 

 

 

 

 

 

 

 

ON/OFF

 

 

 

 

 

 

WALL

 

 

 

 

 

 

SWITCH

 

 

 

 

 

 

 

 

FLAME SPARKER/

 

 

 

 

 

SENSOR

 

 

 

 

IGNITION

 

 

 

 

 

 

MODULE

 

 

 

 

 

 

(3V)

 

 

 

 

 

 

 

 

 

 

 

ORG

 

 

 

 

 

 

WHT

 

VALVE

LOW VOLTAGE

 

 

GROUND TO

 

 

SEE NOTE 1

 

 

FIREPLACE

 

 

 

 

 

 

CHASSIS

 

GROUND

REMOTE

 

 

 

 

NEUTRAL

 

CONTROL

HOT

 

BRN

 

 

 

 

 

BRN

 

 

 

WHITE WIRE

 

 

 

 

 

CAN BE

 

ORG

 

 

 

PLUGGED

 

 

 

 

INTO ANY

 

GRN

BLACK WIRE CAN BE

 

OF #1-#5

 

PLUGGED INTO ANY OF

 

LOCATIONS

PIGGYBACK

 

#1 - #5 LOCATIONS

 

ON THE

ON/OFF SWITCH

 

ON THE HOT SIDE

 

NEUTRAL SIDE

TRANSFORMER

 

 

 

 

 

 

3 VAC

 

 

 

 

 

PLUG IN

 

 

 

 

 

 

 

 

VALVE

 

Figure 23. Intermittent Pilot Ignition (IPI) Wiring Diagram

 

 

Step 8. Wiring the Fireplace

 

 

Optional Accessories

 

 

NOTE: Electrical wiring must be installed by a licensed electrician.

CAUTION: DISCONNECT REMOTE CONTROLS IF YOU ARE ABSENT FOR EXTENDED TIME PERIODS. THIS WILL PREVENT ACCIDENTAL FIREPLACE OPERATION.

Intermittent Pilot Ignition (IPI) Wiring

Appliance Requirements

This appliance requires that 110-120 VAC be wired to the factory installed junction box. Maintain correct polarity when wiring the junction box.

!WARNING: DO NOT CONNECT 110-120 VAC TO THE GAS CONTROL VALVE OR THE AP- PLIANCE WILL MALFUNCTION AND THE VALVE WILL BE DESTROYED.

Optional remote control kits require that 110-120 VAC be wired to the factory installed junction box before the fire- place is permanently installed.

Wall Switch

Position the wall switch in the desired position on the wall. An assembly of 18 ft of 20 AWG is provided with the fire- place to connect the wall switch to the appliance. Instead of the supplied assembly, wire with a length of 25 ft or less and a gauge of 20 AWG through 14 AWG is acceptable. The wire needs a jacket with a temperature rating of 140oF (60oC) or higher. At the appliance connect the wire to the ON/OFF switch pigtails.

!WARNING: DO NOT CONNECT 110-120 VAC TO THE WALL SWITCH OR THE CONTROL VALVE WILL BE DESTROYED.

CAUTION: LABEL ALL WIRES PRIOR TO DISCONNEC- TION WHEN SERVICING CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERA- TION. VERIFY PROPER OPERATION AFTER SERVICING.

Heat & Glo • Everest • 750-900 Rev. L • 1/06

23

Page 23
Image 23
Heat & Glo LifeStyle EVEREST manual Wiring the Fireplace, Optional Accessories, Intermittent Pilot Ignition IPI Wiring