Heat & Glo LifeStyle st-42tvfl manual Step Gas Pressure Requirements, Gas Supply Line, Natural Gas

Models: st-42tvfl

1 31
Download 31 pages 25.27 Kb
Page 23
Image 23
Step 8

At the gas line access hole, use insulation to re- pack the space around the gas pipe.

Insert insulation from the outside of the fireplace and pack the insulation tightly to totally seal between the pipe and the outer casing.

The gas line should be installed by a qualified service technician.

GAS LINEFigure 10. Gas Supply Line ACCESS

USE A WRENCH ON

SHUT-OFF VALVE

WHEN TIGHTENING

GAS LINE

MANUAL

SHUT-OFF

VALVE

GAS VALVE Pressure

FLEX CONNECTOR

Step 8

Gas Pressure

Requirements

Figure 10. Gas Supply Line

Pressure requirements for Heat-N-Glo gas fireplaces are shown in the table below.

Pressure

Natural Gas

Propane

 

 

 

Minimum

5.0 inches

11.0 inches

Inlet Pressure

w.c.

w.c.

 

 

 

Maximum Inlet

14.0 inches

14.0 inches

Gas Pressure

w.c.

w.c.

 

 

 

Manifold

3.5 inches

10.0 inches

Pressure

w.c.

w.c.

A one-eighth (1/8) inch (3 mm) N.P.T. plugged tapping is provided on the inlet and outlet side of the gas control for a test gauge connection to measure the manifold pressure.

The fireplace and its individual shut-off valve must be disconnected from the gas supply piping system during any pressure testing of the system at test pressures in excess of one-half (1/2) psig (3.5 kPa).

The fireplace must be isolated from the gas supply piping system by closing its individual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than one-half (1/2) psig (3.5 kPa).

23

Page 23
Image 23
Heat & Glo LifeStyle st-42tvfl manual Step Gas Pressure Requirements, Gas Supply Line, Natural Gas, Propane