Step 4
Installing the
Vent System
18
A. Vent System Approvals
These fireplaces are approved to use
These models may also use single wall rigid or flexible gas vent IF and ONLY IF the vent system is installed within
The flame and ember appearance may vary based on the type of fuel burned and the venting configuration used.
B. System Components.
Vent System Configuration
MAXIMUM TOTAL HORIZONTAL RUN = 17 FT.
MINIMUM TOTAL VERTICAL RISE = 10 FT.
MAXIMUM NO. of ELBOWS: 2 - 90o or 4 - 45o
Plan and install the vent system using the parameters shown above.
WARNING: YOU MUST NOT EXCEED
!THESE PARAMETERS.
Connect a
A
not exceed a MAXIMUM of
Continue to add vent components, until the vent run is completed.
WARNING: YOU MUST NOT EXCEED A ! TOTAL MAXIMUM HORIZONTAL RUN OF 17 FEET FOR THE ENTIRE VENT SYSTEM.
NOTE: The vent termination must be in a vertical position and the termination cap must be listed for the vent pipe used.
Consult local building code officials and codes for proper vent system installations.