FIGURE 11

2. THIMBLE:

An approved thimble must be used when the connection from the stove is made through a combustible wall to a masonry chimney. There are several methods you can use for connection through a combustible wall, two of which are illustrated in this manual. For additional methods, consult local build- ing authorities or use the standards set forth in NFPA 211.

Also, listed prefabricated metal thimbles are available for use with wood stoves. The manufacturer’s in- stallation for the thimbles must be strictly followed to assure the safety of the system. Be sure to maintain the designated clearances to combustible materials.

A. BRICK CHIMNEY THIMBLE

ASSEMBLY:

Construction of the brick thimble as- sembly requires 12" (305mm) of brick around a fire clay liner. Be sure the point of penetration allows an 18"

(457mm) clearance from the connector to the ceil- ing. For a 6" (152mm) chimney connector, an open- ing of 30" (762mm) must be cut in the wall to main- tain the required 12" (305mm) of brick separation from combustibles. It will be necessary to cut wall studs and install a header and sill frame to main- tain proper dimensions and to hold the weight of the brick (Figure 11).

Chimney

Wall

10

Page 10
Image 10
Heat & Glo LifeStyle WS-150, WS-250 installation instructions Brick Chimney Thimble Assembly