MAIN BURNER FLAME SUSTAINED
YES
NO
NOTE: IF THE SYSTEM GOES INTO LOCKOUT, WAIT 30 SECONDS AND RESET THE SYSTEM.
• CHECK FLAME SENSOR POSITION AND CONDITION
• CLEAN FLAME SENSOR WITH STEEL WOOL
YES
REPLACE SENSOR
• CHECK FLAME SENSOR WIRES AND CONNECTIONS
NO
REPLACE IGNITION CON-
TROL
INDOOR BLOWER MOTOR STARTS | NO | |
| ||
AFTER 30 SECONDS |
| |
|
|
|
| YES |
|
|
|
|
SYSTEM RUNS UNTIL | NO | ||
| |||
CALL FOR HEAT ENDS |
| ||
|
|
| |
| YES |
| |
|
| NO | |
|
| ||
TURN THERMOSTAT OFF | |||
| |||
VALVE SHUTS OFF |
| ||
FLAME SHUTS OFF |
| ||
|
|
| |
| YES |
| |
|
|
|
INDUCED DRAFT MOTOR STOPS | NO |
AFTER 5 SECOND POSTPURGE
YES
• CHECK FOR | NO |
| |||
MOTOR TERMINALS ON CONTROL BOARD |
|
| |||
|
|
| |||
• CHECK CAPACITOR |
|
| |||
|
|
|
|
|
|
|
| YES |
|
| |
|
|
|
|
|
|
|
|
|
|
| |
| REPLACE BLOWER |
|
|
| |
| MOTOR |
|
|
| |
|
|
|
| YES |
|
|
|
|
|
| |
• CHECK FOR OPEN LIMIT |
| ||||
|
| ||||
YES |
| ||||
|
|
|
|
| |
• CHECK FOR OPEN |
| ||||
|
| ||||
|
|
| |||
|
|
| |||
|
|
|
|
|
|
• CHECK FOR PROPER THERMOSTAT OPERATION |
|
| |||
• REMOVE VALVE LEAD AT GAS VALVE |
|
| |||
IF VALVE CLOSES, RECHECK THE THERMOSTAT |
|
| |||
AND WIRING. IF OK, THEN REPLACE VALVE |
|
| |||
|
|
|
|
|
|
REPLACE INTEGRATED CONTROL BOARD (IFC)
•CHECK FOR DIRTY FILTERS
•CHECK FOR RESTRICTED
CHECK FOR EXHAUST,
INTAKE OR HEAT EXCHANG-
ER BLOCKAGE
CLEAR BLOCKAGE AND
RESET CONTROL
INDOOR BLOWER MOTOR STOPS | NO |
AFTER 90 SECONDS
YES
TROUBLESHOOTING ENDS
REPEAT PROCEDURE UNTIL TROUBLE FREE
OPERATION IS OBTAINED.
•CHECK FOR OPEN LIMIT OR
•CHECK FOR EXHAUST OR INTAKE BLOCKAGE. CLEAR BLOCKAGE AND RESET CONTROL
•CHECK FOR DIRTY FILTERS
•CHECK FOR RESTRICTED AIRFLOW
NO
REPLACE INTEGRATED CONTROL BOARD (IFC)