Hitachi SJ-PB(T) Profidrive specific parameters, Operating, 1Profidrive parameters

Models: SJ-PB(T)

1 35
Download 35 pages 2.94 Kb
Page 23
Image 23
5.5 Profidrive specific parameters

CHAPTER5 OPERATING

5.5 Profidrive specific parameters

The table below shows which Profidrive specific parameters that are supported by the SJ-PB(T).

Table 5-1 Profidrive parameters

PNU -

 

 

 

 

 

Parameter Number

Description

 

 

Range

 

915

Refer to chapter 5.3.3 and 5.4.3 for how to assign PZD

Parameter range:

R/W

words. Use the parameter cross-reference list in

1 – 418.

 

Assignment of PZD write word

chapter 5.

 

 

Sub-index range:

 

3-10

Please note: Parameters will be lost when turning

1 – 8.

 

 

power off unless parameter 971 has been written with

 

 

 

“0->1”.

 

 

 

 

916

Refer to chapter 5.3.3 and 5.4.2 for how to assign PZD

Parameter range:

R/W

words. Use the parameter cross-reference list in

1 – 418.

 

Assignment of PZD read word

chapter 5.

 

 

Sub-index range:

 

3-10

Please note: Parameters will be lost when turning

1 – 8.

 

 

power off unless parameter 971 has been written with

 

 

 

“0->1”.

 

 

 

 

918

Returns address switch setting.

 

1-99

R

 

 

 

 

 

Profibus-DP slave address

 

 

 

 

 

927

1 – PKW interface enabled. Parameters can be

0, 1

R/W

read/written.

 

 

 

 

Parameter edit rights

0 – PKW interface disabled, only parameter 927 can

 

 

 

be read/written.

 

 

 

 

928

1 – Option board will send control word, reference and

0, 1

R/W

will update PZD3-10.

 

 

 

Control rights (process data).

0 – PZD not enabled.

 

 

 

947

Fault. Codes as described in table 5-2 below.

-

R

Sub-index 1 = Not acknowledged fault.

 

 

Indexed Fault memory

Sub-index 9 = Latest acknowledged fault.

 

 

 

Sub-index 17 = 2nd latest acknowledged fault.

 

 

 

Sub-index 25 = 3rd latest acknowledged fault.

 

 

 

Sub-index 33 = 4th latest acknowledged fault.

 

 

 

Sub-index 41 = 5th latest acknowledged fault.

 

 

 

Sub-index 49 = 6th latest acknowledged fault.

 

 

963

the baudrate of the Profibus-DP network

0-9

R

0: 12 Mbit/s 1: 6 Mbit/s 2: 3 Mbit/s 3: 1.5 Mbit/s

 

 

PROFIBUS-DP baud rate

4: 500 kbit/s

5: 187.5 kbit/s

6: 93.75 kbit/s

 

 

 

7: 45.45 kbit/s

8: 19.2 kbit/s

9: 9.6 kbit/s

 

 

964

Bit 15 represents the type of inverter, 0 – SJxxx, 1 –

012Ch, 812Ch

R

LxxxP. Rest of the word represents the model number.

 

 

Device identification

SJ300 - 0x012C

 

 

 

 

L300P - 0x812C

 

 

 

965

Returns the Profidrive profile version used in the SJ-PB

2

R

implementation

 

 

 

 

Profile version

 

 

 

 

 

967

Shows the latest received control word in hex format

Bit 0-15

R

Refer to chapter 5.3.1 for detailed information about

 

 

Control Word

the control word.

 

 

 

968

Shows the latest status word in hex format

Bit 0-15

R

Refer to chapter 5.3.1 for detailed information about

 

 

Status Word

the status word.

 

 

 

971

Please note that it will take approximately 10s for this

0, 1

W

process to finish (inverter must be stopped).

 

 

Transfer into non-volatile

0 – No function.

 

 

 

memory

1 – Will save inverter parameters to non-volatile

 

 

 

memory and the Profile specific parameters to FLASH.

 

 

19

Page 23
Image 23
Hitachi SJ-PB(T) instruction manual Profidrive specific parameters, Operating, 1Profidrive parameters