3-13. Selecting A Location And Connecting Input Power
Y Do not move or operate unit where it could tip.
18 in (457 mm) of space for airflow
| 1 |
|
8 |
| =GND/PE Earth Ground |
| 10 |
|
| 7 |
|
| 9 |
|
| L1 | 4 |
| L2 | |
|
| |
5 |
|
|
| 6 |
|
2
1
3
L2L1
230 VAC, 1
YInstallation must meet all Na- tional and Local Codes − have only qualified persons make this installation.
YSpecial installation may be required where gasoline or volatile liquids are present − see NEC Article 511 or CEC Section 20.
YDisconnect and lockout/tag- out input power before con- necting input conductors from unit.
YAlways connect green or green/yellow conductor to supply grounding terminal
first, and never to a line ter- minal.
1 Rating Label
Supply correct input power.
2Plug
3Receptacle
Connect plug to receptacle.
4Black And White Input Conductor (L1 And L2)
5Green Or Green/Yellow Grounding Conductor
6Input Power Cord.
7Disconnect Device (switch shown in the OFF position)
8Disconnect Device Grounding Terminal
9Disconnect Device Line Terminals
Connect green or green/yellow grounding conductor to disconnect device grounding terminal first.
Connect input conductors L1 and L2 to disconnect device line termi- nals.
10
Select type and size of
Close and secure door on discon- nect device. Remove lockout/tag- out device, and place switch in the On position.