3-12. Electrical Service Guide

 

60 Hz Single

 

 

Phase

 

 

 

Input Voltage

200

 

230

 

 

 

 

Input Amperes At Rated Output

40

 

35

 

 

 

 

Max Recommended Standard Fuse Rating In Amperes

 

 

 

Circuit Breaker 1, Time-Delay 2

50

 

40

Normal Operating 3

60

 

50

Min Input Conductor Size In AWG 4

8

 

10

Max Recommended Input Conductor Length In Feet (Meters)

108

 

94

(33)

 

(29)

 

 

 

 

 

 

Min Grounding Conductor Size In AWG 4

10

 

10

Reference: 2005 National Electrical Code (NEC) (including article 630)

1Choose a circuit breaker with time-current curves comparable to a Time Delay Fuse.

2“Time-Delay” fuses are UL class “RK5” .

3“Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and above).

4Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table 310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.

YCaution: Failure to follow these fuse and circuit breaker recommendations could create an electric shock or fire hazard. These recommendations are for a dedicated branch circuit that applies to the rated output and duty cycle of the welding power source.