power monitoring is a configuration that allows TrueSTEAM to only allow humidity to enter
the duct when it receives confirmation that the HVAC system transformer has power.
Therearetwowayspowermonitoringcanbeconfigured,depending onwhathumiditycontrolis
used.
1. using a thermostat with integrated humidity
control, such as Visionpro Iaq or prestige.
• Athermostatispoweredbythesystemtransformer,
soifitdoesnothavepower,thehumidifierwillnot
be able to produce steam.
• Becausethethermostatknowswhenthesystem
transformerhaspower,setTrueSTEAMDIP4toUP,
so that it is not also looking for an R input from the
system R.
Ideal for contractors Who
- Want simplified accessory wiring (TrueSTEAM only
needs to be connected to the HUM terminals from the control).
- Provide integrated system and accessory controls in the living space to their customers.
2. using a humidistat separate from the
thermostat, such as h8908 or trueIaq.
• TrueSTEAMgenerallysuppliespowertoa
humidistat. It is important that TrueSTEAM monitor
HVAC system power to determine if humidity is
allowed.
• LeaveDIP4intheDOWNposition(factory
setting),andwiretheHVACsystemRandCtothe
TrueSTEAM R and C. TrueSTEAM will verify power
is present before allowing steam production.
Ideal for contractors Who
- Use a humidity control separate from the thermostat system control.
M28684
1
2
3R
C
HUM
HUM
DIP 4
M28685
R
C
HUM
HUM
DIP 4
note: This image is not a complete wiring diagram.
It only depicts power monitoring.
note: This image is not a complete wiring diagram.
It only depicts power monitoring.
WIrInG–GettInG started