ST 3000 Release 300 and SFC Model STS103 User’s Manual 6/08
150
7.11 Liquid Level Measurement with DP Transmitter with
Remote Seals, Continued

Procedure, continued

Table 45 Starting Up DP Transmitter with Remote Seals for Liquid Level Measurement with

SFC, continued

Step Press Key Read Display or Action Description

10 URV
100%
F
SET
G
NON-VOL
ENTER
(Yes)
PTURV 3Ø111
5.Ø ØØØ "H2O
_39F
PTUR V
RV
11
U
1
?SET
PTURV 3Ø1 11
.536Ø1"H2O
_39F
Read present URV setting.
Prompt asks if you want to set URV
to applied pressure.
URV is set to full tank pressure.
11 INPUTJ
OUT-
PUT
PTOU T 3Ø1 11P
FC WOSING.RK ..
%
.PTOU T 3Ø1 11P
.ØØØ
Call up output for display, with full
tank pressure applied.
Read 100% output on display for
corresponding full tank pressure.
For analog transmission, check that
milliammeter reading is 20 mA
(100%) output.
12 Take SFC and milliammeter readings to
check that output signal does
correspond to empty and full tank
pressures. If readings don’t correspond,
check that transmitter has been installed
correctly. If applicable, blow down piping
to be sure no foreign matter is entrapped
in it. Check SFC and milliammeter
readings again. If readings are still not
correct, verify transmitter’s configuration
data and change its range setting if
needed.
13 Remove SFC and milliammeter from
loop.