ST 3000 Release 300 and SFC Model STS103 User’s Manual 6/08
66
6.2 Overview, Continued

Configuration

decision summary The flowchart in Figure 25 summarizes the typical entries/selections

decisions associated with configuring an ST 3000 pressure transmitter.

Figure 25 Flowchart — ST 3000 Pressure Transmitter Configuration.

Ha ve yo u
assigned a unique
"tag number" for
the transmitter?
Start
NO
YES
Assign a unique t ag number consisting of up t o 8
alph anumeric charac ter s to i den tif y this transmit ter.
Establi s h communications and
enter assigned Tag Num ber at
SFC conf igur ation pr ompt TAG
NO.
See pro cedure in Table 21 for entry details.
Press [ID] key and acknowledge T RIPS SECURED p rompt, if
req uire d , to call up SF C prom p t TAG NO. Use [NUM/ALPHA]
key to toggle between Alpha mode an d Nu meric mode to
enter alphabetic characters and numbers, respective ly,
through SFC keys.
Do you know i f
output is to represent
linear or square root
calculation?
NO
YES
Determine if transmitter's output is to represent a
straight linear calculation or a square root calculation
for flow measurements.
Select LINEAR or SQUARE ROOT
thro ugh SFC configuratio n
prompt CONFORMITY.
See procedure in Table 22 for selection details.
Call up SFC configuration prompt CONFORMITY and select
menu item LINEAR or SQUARE ROOT.

A

Continued on next page