ST 3000 Release 300 and SFC Model STS103 User’s Manual 6/08
82
6.7 Setting Range Values Using SFC, Continued

Procedure 2 Table 26 gives the procedure for setting range values to sample applied

pressures.

Table 26 Setting LRV and URV to Applied Pressures

Step Press Key Read Display or Action Description

1 Apply known input pressure to
transmitter that represents LRV for 0%
(4 mAdc) output.
2 E
LRV
0%
PTLRV 3Ø111
5. ØØØØ "H2O
_39F
Present LRV setting. (Pressure for 4
mAdc (0%) output.)
3 SET
G
PTLRV
RV
11
L
1
?SET
Prompt asks if you want to set LRV
to applied pressure. If you don’t
want to set LRV, press [CLR] key to
exit function. Otherwise, go to Step
4.
4 NON-VOL
ENTER
(Yes)
ORK NGCW .F.S.I
PTLRV 3Ø111
PTLRV 3Ø111
7. 8377 "H2O
_39F
Message exchange is working.
Applied LRV setting stored in
transmitter's working memory.
5 Apply known input pressure to
transmitter that represents URV for
100% (20 mAdc) output.
6 URV
100%
F
PTURV 3Ø1 11
4.7 837 "H2O
_39F
Present URV setting. (Pressure for
20 mAdc (100%) output.)
7 SET
G
PTUR V
RV
11
U
1
?SET
Prompt asks if you want to set URV
to applied pressure. If you don’t
want to set URV, press [CLR] key to
exit function. Otherwise, go to Step
8.
8 NON-VOL
ENTER
(Yes)
ORK NGCW .F.S.I
PTURV 3Ø1 11
PTURV 3Ø1 11
5.5 482
Message exchange is working.
Applied URV setting stored in
transmitter’s working memory.
Continued on next page