G. Alarm Safeties

G. Alarm Safeties

The alarms are designed to protect the appliance and the items inside. These alarms give information and warnings in the event the appliance is operating out of acceptable parameters. For all alarms except Pr1, the alarm icon a) High and Low Temperature Alarm Values (AH or AL)Manual background turns on and the alarm code alternates with the cabinet temperature. If the Pr1 alarm occurs, only Pr1 and the alarm icon Manual backgroundManual background are displayed.

Alarm Signals

Alarm Code

Problem

Corrective Action/Reset Details

 

 

 

 

High Temperature Alarm

If obvious corrections such as closing the door and

 

 

cleaning the condenser do not bring temperature

AH

Cabinet temperature has exceeded the

back in range, see "IV. Service Diagnosis."

setpoint temperature by 10°F for more

 

 

 

 

than 2 hours.

Automatically resets when temperature returns to

 

 

normal. Alarm icon flashes until reset manually.

 

 

 

 

Low Temperature Alarm

If obvious corrections do not bring the temperature

 

 

back in range, see "IV. Service Diagnosis."

AL

Cabinet temperature has remained below

 

 

the setpoint temperature by 10°F for more

Automatically resets when temperature returns to

 

than 2 hours.

normal. Alarm icon flashes until reset manually.

 

 

 

Ld

Door Open

Close the door.

 

 

 

 

Cabinet Thermistor Malfunction Alarm

Compressor and evaporator fan motor cycle 10 min.

Pr1

 

on, 10 min. off.

 

Cabinet thermistor has failed.

 

a) High and Low Temperature Alarm Values (AH or AL)

If an AH or AL alarm occurs, follow the steps below to acquire alarm details.

1)Press the "-" button for 3 sec. to enter the alarm menu. "EnS" is displayed.

2)Press the "+" button once. "LS" is displayed.

3)Press the "P" button. The alarm code is displayed.

4)Press the "P" button again and the alarm details are displayed in 2 second increments.

AH or AL Alarm code

XX°F The highest or lowest temperature during the alarm

dur Alarm duration

h01 Hours alarm has been engaged

n15 Minutes alarm has been engaged (continuance of h01)

To review, press the "P" button again.

To exit, press the on/off button twice. After pressing the on/off button the first time, "LS" is displayed. After pressing the on/off button the second time, the display returns to the alarm code display.