Defrost (Do Not Adjust)
Service Menu | Min. | Max. | Unit | Factory Setting | Description |
|
|
|
|
|
|
d0 | 0 | 99 | hrs. | 6 | Defrost interval: |
|
|
|
|
| 0=no defrost |
d1 | 0 | 2 | 2 | Defrost type. Do not adjust. | |
|
|
|
|
| 0=electric heater |
|
|
|
|
| 1=hot gas |
|
|
|
|
| 2=off cycle (evaporator fan motor) |
|
|
|
|
|
|
d2 | 99 | °C/°F | N/A | Limit for defrost if P3 = 1 or 2. | |
|
|
|
|
|
|
d3 | 0 | 99 | min. | 30 | Defrost duration. |
|
|
|
|
|
|
d4 | 0 | 1 | 0 | Defrost on startup. Do not adjust. | |
|
|
|
|
| 0=no, 1=yes |
d5 | 0 | 99 | min. | 0 | Minimum time between startup and |
|
|
|
|
| defrost. Do not adjust. |
d6 | 0 | 1 | 0 | Temperature display | |
|
|
|
|
| during defrost. Do not adjust. |
|
|
|
|
| 0=cabinet temperature |
|
|
|
|
| 1=cabinet temperature or setpoint |
|
|
|
|
| + differential (4°F). Based on |
|
|
|
|
| cabinet temperature at defrost |
|
|
|
|
| initiation. |
|
|
|
|
|
|
d7 | 0 | 15 | min. | 0 | Drip time. Do not adjust. |
|
|
|
|
|
|
d8 | 0 | 3 | 0 | Defrost initiation. Do not adjust. | |
|
|
|
|
| 0=d0 defrost timer is cumulative |
|
|
|
|
| power on time. |
|
|
|
|
| 1=d0 defrost timer is cumulative |
|
|
|
|
| compressor run time. |
|
|
|
|
| 2=defrost starts when |
|
|
|
|
| evaporator temperature < d9 |
|
|
|
|
| for time d0. |
|
|
|
|
| 3=based on evaporator temperature |
|
|
|
|
| when evaporator thermistor is |
|
|
|
|
| present. |
|
|
|
|
|
|
d9 | 99 | °C/°F | 32 | Do not adjust. | |
d10 | 0 | 99 | °C/°F | 27 | Do not adjust. |
|
|
|
|
|
|
d11 | 0 | 1 | 0 | Do not adjust. | |
|
|
|
|
|
|
d12 | 0 | 99 | min. | 30 | Do not adjust. |
|
|
|
|
|
|
d13 | 1 | 240 | min. | 1 | Do not adjust. |
d14 | 0 | 240 | min. | 30 | Do not adjust. |
|
|
|
|
|
|
d15 | 0 | 99 | min. | 0 | Minimum compressor run time before |
|
|
|
|
| defrost if d1=1. Do not adjust. |
|
|
|
|
|
|
20