Hoshizaki HR24A service manual Evaporator Fan Motor Do Not Adjust

Models: HR24A

1 39
Download 39 pages 40.2 Kb
Page 22
Image 22
Evaporator Fan Motor (Do Not Adjust)

Evaporator Fan Motor (Do Not Adjust)

Service Menu

Min.

Max.

Unit

Factory Setting

Description

 

 

 

 

 

 

F0

0

4

---

1

Fan operation with door closed.

 

 

 

 

 

Do not adjust.

 

 

 

 

 

0=off

 

 

 

 

 

1=on: see also F13, F14, and L10

 

 

 

 

 

2=parallel with compressor

 

 

 

 

 

3= dependent on F1

 

 

 

 

 

4=disabled when compressor is off,

 

 

 

 

 

dependent on F1 when

 

 

 

 

 

compressor is on.

 

 

 

 

 

 

F1

-99

99

°C/°F

30

Fan off temperature when F0 set to

 

 

 

 

 

3 or 4. Do not adjust.

 

 

 

 

 

 

F2

0

2

---

1

Fan operation during defrost:

 

 

 

 

 

Do not adjust.

 

 

 

 

 

0=disabled

 

 

 

 

 

1=enabled

 

 

 

 

 

2=dependent on F0

F3

0

15

 

2

Maximum fan off time when defrost

 

 

 

 

 

thermistor used.

 

 

 

 

 

 

F7

-99

99

°C/°F

0

Fan on temperature when defrost

 

 

 

 

 

thermistor used.

 

 

 

 

 

 

F8

0.1

15

°C/°F

4

F1 differential.

 

 

 

 

 

 

F9

0

240

sec.

0

Energy saving evaporator fan motor

 

 

 

 

 

delay after compressor shuts off.

F13

0

240

min.

5

Energy saving evaporator fan motor

 

 

 

 

 

off time.

 

 

 

 

 

 

F14

0

240

min.

1

Energy saving evaporator fan motor

 

 

 

 

 

on time.

 

 

 

 

 

 

Door Switch and Door Alarm (Do Not Adjust)

Service Menu

Min.

Max.

Unit

Factory Setting

Description

 

 

 

 

 

 

L0

0

5

---

2

Door switch function.

 

 

 

 

 

1=compressor and evaporator

 

 

 

 

 

fan motor de-energized

 

 

 

 

 

2=evaporator fan motor

 

 

 

 

 

de‑energized

 

 

 

 

 

3-5=reserved

L1

0

1

---

0

Door switch operation.

 

 

 

 

 

0=normally open

 

 

 

 

 

1=normally closed

 

 

 

 

 

 

L2

-1

120

min.

10

Door alarm time delay.

 

 

 

 

 

-1=deactivated

 

 

 

 

 

 

L3

-1

120

min.

-1

Evaporator fan motor off time

 

 

 

 

 

when door is open.

 

 

 

 

 

-1=until door switch engaged

 

 

 

 

 

 

L4

0

1

---

0

Save door alarm.

 

 

 

 

 

0=no

 

 

 

 

 

1=yes

 

 

 

 

 

 

L10

0

999

min.

20

Energy saving activation.

 

 

 

 

 

After cabinet temperature

 

 

 

 

 

is reached and door switch

 

 

 

 

 

remains closed.

22

Page 22
Image 22
Hoshizaki HR24A service manual Evaporator Fan Motor Do Not Adjust