Specifications
Install
Wiring Diagrams
V. Removal And Replacement Of Components
Maintenance
Complete and detailed explanation of the problem
Check a thermistor for resistance by using the following procedures
Defrost Timer
d CONTROLS AND ADJUSTMENTS
Setting
Page 8
Image 8
4.
KM-900MRF3
* We reserve the right to make changes in specifications and design without prior notice.
8
Page 7
Page 9
Page 8
Image 8
Page 7
Page 9
Contents
MODELS
KM-900MAF KM-900MWF KM-900MRF KM-900MRF3
HOSHIZAKI MODULAR CRESCENT CUBER
Phone 1-800-233-1940 Technical Service
Complete and detailed explanation of the problem
HOSHIZAKI AMERICA, INC 618 Highway 74 South Peachtree City, GA
Attn HOSHIZAKI Technical Support Department
CONTENTS
IV. SERVICE DIAGNOSIS
V. REMOVAL AND REPLACEMENT OF COMPONENTS
SERVICE FOR REFRIGERANT LINES
a REFRIGERANT RECOVERY
I. SPECIFICATIONS 1. KM-900MAF
2. KM-900MWF
3. KM-900MRF
4. KM-900MRF3
5. CONDENSING UNIT URC-12F
SPECIFICATIONS MODEL URC-12F
a KM-900MAF
II. GENERAL INFORMATION
1. CONSTRUCTION
b KM-900MWF
c KM-900MRF
d KM-900MRF3
Features of Control Products “E” Controller Board
2. CONTROLLER BOARD
a SOLID-STATE CONTROL
b CONTROLLER BOARD
2 Defrost Timer
3 High Temperature Safety - 127 ± 7F
4 Low Water Safety
6 LED Lights and Audible Alarm Safeties
1 beep every 3 sec. = High Evaporator Temperature 127 F
1 Minute Fill Cycle
Harvest Cycle
Freeze Cycle
Control Products HOS-001A Board
c SEQUENCE 1st Cycle
IMPORTANT Water Valve opening is limited to 6 minutes
2nd Cycle and after with pump drain
IMPORTANT Water Valve opening is limited to 6 minutes
2nd Cycle and after with no pump drain
IMPORTANT Water Valve opening is limited to 6 minutes
d CONTROLS AND ADJUSTMENTS
Temperature F
Check a thermistor for resistance by using the following procedures
i Disconnect the connector K3 on the board
2 Defrost Timer
3 Drain Timer
The Drain Timer is factory-adjusted, and no adjustment is required
SETTING
Dip Switch
e CHECKING THE CONTROLLER BOARD
At this point, the unit should start the defrost cycle
After the 1 minute water supply cycle, the defrost cycle starts
III. TECHNICAL INFORMATION
1. WATER CIRCUIT AND REFRIGERANT CIRCUIT a KM-900MAF
b KM-900MWF
c KM-900MRF and KM-900MRF3
2. WIRING DIAGRAMS
a KM-900MAF
Note Pressure Switch
b KM-900MWF
Cut-out
412 ±
Note Pressure Switch
c KM-900MRF
Cut-out
412 ±
Note Pressure Switch
d KM-900MRF3
Cut-out
412 ±
From Defrost Cycle To Defrost Cycle
3. TIMING CHART
If Float Sw. is OFF
To Freeze Cycle From Freeze Cycle
Control
4. PERFORMANCE DATA a KM-900MAF
b KM-900MWF
c KM-900MRF
b KM-900MRF3
IV. SERVICE DIAGNOSIS 1. NO ICE PRODUCTION
PROBLEM
POSSIBLE CAUSE
REMEDY
REMEDY
PROBLEM
POSSIBLE CAUSE
REMEDY
PROBLEM
POSSIBLE CAUSE
a See chart 1 - 3, and check dirty Air Filter or Condenser
2. EVAPORATOR IS FROZEN UP
3. LOW ICE PRODUCTION
Solenoid Valve, water system
4. ABNORMAL ICE
5. OTHERS
V. REMOVAL AND REPLACEMENT OF COMPONENTS
1. SERVICE FOR REFRIGERANT LINES
a REFRIGERANT RECOVERY
b EVACUATION AND RECHARGE R-404A
2. BRAZING DANGER
3. REMOVAL AND REPLACEMENT OF COMPRESSOR IMPORTANT
18 Turn on the power supply
17 Replace the panels in their correct positions
4. REMOVAL AND REPLACEMENT OF DRIER
5. REMOVAL AND REPLACEMENT OF EXPANSION VALVE
6. REMOVAL AND REPLACEMENT OF HOT GAS VALVE AND LINE VALVE
1 Turn off the power supply 2 Remove the panels
3 Recover the refrigerant and store it in an approved container
5 Disconnect the Hot Gas Valve or Line Valve using brazing equipment
6 Install the new valve
7. REMOVAL AND REPLACEMENT OF EVAPORATOR IMPORTANT
Page
9. ADJUSTMENT OF WATER REGULATING VALVE - WATER-COOLED MODEL ONLY
Page
11. REMOVAL AND REPLACEMENT OF THERMISTOR CAUTION
Thermistor Lead
Cable Tie
Foam Insulation
12. REMOVAL AND REPLACEMENT OF FAN MOTOR
Min. 4-3/4 Liquid Bypass Flow
13. REMOVAL AND REPLACEMENT OF WATER VALVE
14. REMOVAL AND REPLACEMENT OF PUMP MOTOR
15. REMOVAL AND REPLACEMENT OF SPRAY TUBES
VI. MAINTENANCE AND CLEANING INSTRUCTIONS
1. PREPARING THE ICEMAKER FOR LONG STORAGE
2 Move the Control Switch, on the Control Box, to the “OFF” position
7 Move the Control Switch to the “ICE” position
3 Drain the Potable Water Tank 1 Turn off the power supply
2 Move the Control Switch to the “OFF” position
OPEN POSITION
2. CLEANING
CLOSED POSITION
a CLEANING PROCEDURE
b SANITIZING PROCEDURE - Following Cleaning Procedure
3. MAINTENANCE