F. Installation of Remote Condenser Unit

1.Checks Before Installation

1)Remove the shipping carton, tape, and packing material.

2)Check that the refrigerant lines do not rub or touch lines or other surfaces, and that the fan blade moves freely.

2.Location

IMPORTANT

The remote condenser unit is intended for outdoor use. Normal operating ambient temperature should be within -20°F to +122°F (-29°C to +50°C). Operation of the remote condenser unit, for extended periods, outside of this normal temperature range may affect icemaker performance.

The remote condenser unit must be positioned in a permanent site under the following guidelines:

A firm and flat site.

A dry and well ventilated area with 24" (61 cm) clearance in both front and rear for ease of maintenance and service should they be required.

The maximum line length for the standard refrigerant charge is 66 feet. Should an installation require a longer line length, additional refrigerant must be added to the system. Add .4 oz. of R-404A for each foot over 66 feet to a maximum of 100 feet or call 1-800-233-1940 for recommendations.

The maximum vertical distance between the remote condenser unit and the icemaker is 33 feet above or 10 feet below the icemaker. These distances are measured fitting to fitting.

CAUTION

Failure to install the equipment within these guidelines may adversely affect performance, component life, and warranty coverage.

Min. 24" (61 cm) Clearance

AirAir

Locate

Legs

Fig. 4

13

Page 13
Image 13