HP 422690 I manual Area PER Diameter Given Pipe Opening

Models: 422690 I

1 27
Download 27 pages 9.71 Kb
Page 13
Image 13

You must provide air sufficient for all gas appliances within furnace space. Locate one combustion and ventilation air opening within 12 inches of top of furnace space. Locate another within 12 inches of bottom of furnace space.

Ducts that supply air from outdoors must have the same cross-sectional area as the free area of openings to which

they connect.

Figure 10. All Air Directly From Spaces That Freely Access The Outdoors.

When directly communicating with the outdoors, each opening must have a minimum free area of one square inch per 4,000 Btu per hour of total combined input rating of all gas appliances within furnace space. For example: A 108,000 Btu per hour furnace requires two openings of at least 108,000 ÷ 4,000 or 27 square inches. See Figure 10 and Table 3.

Table 3. Free Opening Area Based On One Square Inch Per 4000 Btu/hr.

TOTAL

REQUIRED

MINIMUM

MAXIMUM

INPUT

FREE

ROUND PIPE

INPUT FOR

(Btu/hr)

AREA PER

DIAMETER

GIVEN PIPE

 

OPENING

(inches)

DIAMETER

 

(square inches)

 

(Btu/hr)

54,000

13.5

5

78,000

72,000

18

5

78,000

90,000

22.5

6

113,000

108,000

27

6

113,000

126,000

31.5

7

153,000

144,000

36

7

153,000

When communicating with the outdoors through vertical ducts, openings and ducts must have a minimum free area of one square inch per 4,000 Btu per hour of total combined input rating of all gas appliances within furnace space. See Figure 11 and Table 3.

Figure 11. All Air Through Vertical Ducts From Spaces That Freely Access The Outdoors.

Figure 12. All Air From The Outdoors Through Horizontal Ducts.

When communicating with the outdoors through horizontal ducts, openings and ducts must have a minimum free area of one square inch per 2,000 Btu per hour of total combined input rating of all gas appliances within furnace space. See Figure 12 and Table 4.

Table 4. Free Opening Area Based On One Square Inch Per 2000 Btu/hr.

TOTAL

REQUIRED

MINIMUM

MAXIMUM

INPUT

FREE

ROUND

INPUT FOR

(Btu/hr)

AREA PER

PIPE

GIVEN PIPE

 

OPENING

DIAMETER.

DIAMETER

 

(square inches)

(inches)

(Btu/hr)

54,000

27

6

56,000

72,000

36

7

76,000

90,000

45

8

100,000

108,000

54

9

127,000

126,000

63

9

127,000

144,000

72

10

157,000

Example: Furnace is 90,000 Btu per hour input and is to be installed in a confined space that contains no other gas appliances. Rectangular combustion and ventilation air ducts will run horizontally from outdoors to furnace space.

Installer’s Information Manual

Page 13

Page 13
Image 13
HP 422690 I manual Area PER Diameter Given Pipe Opening