HP 422690 I manual Changing Main Burner Orifices, Gas, Heating Value

Models: 422690 I

1 27
Download 27 pages 9.71 Kb
Page 23
Image 23

Table 7. Natural Gas Orifice Size.

 

 

 

 

 

 

 

 

 

 

 

 

ELEVATION

 

 

 

 

GAS

Up

2001

3001

4001

5001

6001*

7001*

8001*

9001*

HEATING

to

to

to

to

to

to

to

to

to

VALUE**

2000

3000

4000

5000

6000

7000

8000

9000

10000

(Btu/cu. ft.)

Feet

Feet

Feet

Feet

Feet

Feet

Feet

Feet

Feet

800-849

2.25

2.20

2.15

2.15

2.10

2.05

2.05

2.00

1.95

850-899

2.20

2.15

2.10

2.10

2.05

2.00

2.00

1.95

1.90

900-949

2.15

2.10

2.05

2.05

2.00

1.95

1.95

1.90

1.85

950-999

2.10

2.05

2.00

2.00

1.95

1.90

1.90

1.85

1.80

1000-1049

2.05

2.00

1.95

1.95

1.90

1.85

1.85

1.80

1.75

1050-1099

2.00

1.95

1.90

1.90

1.85

1.80

1.80

1.75

1.75

1100-1149

1.95

1.90

1.85

1.85

1.80

1.80

1.75

1.75

--

1150-1199

1.90

1.85

1.85

1.80

1.75

1.75

--

--

--

*Above 6000 feet, a high-altitude gas conversion kit must be used.

**At standard conditions: 30.0 inches Mercury, 60°F, Saturated.

Table 8. Propane (LP) Gas Orifice Size.

 

 

 

 

 

 

 

GAS

 

 

 

 

ELEVATION

 

 

 

 

Up

2001

3001

4001

5001

6001*

7001*

8001*

9001*

HEATING*

to

to

to

to

to

to

to

to

to

VALUE

2000

3000

4000

5000

6000

7000

8000

9000

10000

(Btu/cu. ft.)

Feet

Feet

Feet

Feet

Feet

Feet

Feet

Feet

Feet

2500-2550

1.20

1.15

1.15

1.15

1.15

1.10

1.10

1.10

1.05

* Above 6000 feet, a high-altitude gas conversion kit must be used.

SECTION 17. CHANGING MAIN BURNER ORIFICES

WARNING: To prevent electrical shock and gas leaks, turn off electrical power and gas before changing

orifices.

Follow this procedure:

1.Turn off electricity at electrical disconnect switch next to furnace.

2.Turn off equipment shut-off valve in gas supply line just ahead of furnace.

3.Remove three screws holding burner access panel in place. Remove burner access panel.

4.Starting with burner farthest from gas control, remove main burner screws and main burners. Note how burners overlap. Burner farthest from gas control is on top. See Figure 21.

5.Remove original main burner orifices from manifold pipe.

6.Carefully, hand thread new orifices into manifold pipe. Do not cross-thread. Tighten to torque of 50 inch- pounds.

7.Starting with burner closest to gas control, replace main burners and main burner screws. Burner mounting flange of burner farther from gas control overlaps burner-mounting flange of burner closest to gas control.

Figure 21. Main Burner Removal.

8.Check burner carry-over alignment. Burner carry- overs may touch but not overlap adjacent burner carry- overs. Replace screws .

9.Replace burner access panel using three screws removed in step 3.

10.Open equipment shut-off valve in gas supply line just ahead of furnace.

11.Set room thermostat to highest setting and to heating mode.

12.Turn on electricity at electrical disconnect switch located next to furnace. Furnace will light.

13.Visually check that each burner lights promptly.

14.Check gas input following Section 14, "Checking Gas Input Rate."

15.Reset room thermostat to desired setting.

Installer’s Information Manual

Page 23

Page 23
Image 23
HP 422690 I manual Changing Main Burner Orifices, Gas, Heating Value