QuickSpecs

HP AlphaServer GS1280 Systems

Technical Specifications

 

GS1280 Model 8

GS1280 Model 16

GS1280 Model 32

GS1280 Model 64

 

1 I/O Drawer, 1 SW

1 I/O Drawer, 1 SW

1 I/O Drawer, 1 SW

1 I/O Drawer, 1 SW

 

Shelf

Shelf

Shelf

Shelf

Power Required, Kva

3.5

5.7

10.1

18.7

Power Distribution Unit

1 required; 2 for dual

2 required; 4 for dual

2 required, dual AC

2 required, dual AC

(PDU) required for all

AC

AC

included

included

GS1280 Models 3X-H7606-

 

 

 

 

Ax

 

 

 

 

Power Distribution Unit

Not applicable

Not applicable

2 required, dual AC

4 required, dual AC

(PDU) required for GS 1280

 

 

included

included

Models 32 and 64, 3X-

 

 

 

 

H7606-Bx

 

 

 

 

 

 

 

 

 

Physical Characteristics

 

 

 

 

Dimensions (H x W x D)

79 x 24 x 47 in (200 x 60 120 cm) (one 41U Rack)

 

Shipping Dimensions

86 x 32 x 48 in (217 x 92.5 142 cm) (one 41U Rack)

 

 

GS1280 Model 8

GS1280 Model 16

GS1280 Model 32

GS1280 Model 64

Installed Weight, base system 870 lb (395 kg)

1,272 lb (577 kg)

2,118 lbs (961 kg)

4,800 lbs (2,176 kg)

Heat dissipation

 

 

 

 

Max Heat Output, Base Model 3,405

6,810

14,820

28,440

only, watts

 

 

 

 

Max heat Output, Base Model

11,622

23,243

50,581

97,066

only, Btu/hr

 

 

 

 

Typical Heat Output, Base

2,430

3,700

8,000

14,800

Model only, watts

 

 

 

 

Typical Heat Output, Base

8,297

12,632

27,304

50,513

Model only, Btu/hr

 

 

 

 

Airflow, cfm, minimum full

912

1,562

1,800

1,800 x 2 racks

rack, each CPU rack

 

 

 

 

Airflow, cfm, maximum full

1,404

2,454

3,400

3,400 x 2 racks

rack, each CPU rack

 

 

 

 

Airflow, cfm, minimum full

 

 

1,324

1,455

rack, power rack for Model 32

 

 

 

 

and 64

 

 

 

 

Airflow, cfm, maximum full

 

 

1,508

1,685

rack, power rack for Model 32

 

 

 

 

and 64

 

 

 

 

 

 

 

 

 