3 Functions

Issue 07/04

U, M, P, Φ

 

 

U, P

 

Rated motor

Mn, Φ n

operating point

U, P

M, Φ

 

 

f

Voltage control range

Field control range

fn

fmax

Fig. 3-61 Operating ranges and characteristics of an induction motor when fed from a drive inverter

There are several versions of the V/f characteristic as shown in Table 3-27.

Table 3-27 V/f characteristic (parameter P1300)

Parameter

Significance

Use / property

 

 

value

 

 

 

 

0

Linear

Standard case

V

 

 

character-

 

 

 

 

istic

 

Vn

 

 

 

 

 

P1300 = 0

 

 

 

0

f

 

 

 

fn

1

FCC

Characteristic which compensates the voltage losses of the stator

 

 

resistance for static (steady-state) or dynamic loads (flux current control

 

 

FCC). This is especially used for small motors which have a relatively high

 

 

stator resistance. Refer to Section 3.21.1.2.

 

2

Square-law

This is a characteristic which

V

 

 

character- takes into consideration the

 

 

 

istic

torque characteristic of the driven

Vn

 

 

 

load (e.g. fan / pump)

 

 

 

 

a) Square-law characteristic

 

 

 

 

(f 2 characteristic)

 

 

 

 

b) Energy saving as the lower

 

 

 

 

voltage also results in lower

 

 

 

 

currents and losses.

 

P1300 = 2

 

 

 

 

 

 

 

0

f

3

Programm-

Characteristic which takes into

fn

V

 

 

able

consideration the torque

 

 

Vmax

 

 

character- characteristic of the motor /

r0071

 

 

Vn

 

 

istic

driven load (e.g. synchronous

 

 

P0304

P1300 = 3

 

 

motor).

 

 

 

P1325

 

 

 

 

 

 

 

 

P1323

 

 

 

 

P1321

 

 

 

 

P1310

 

 

 

 

 

 

 

 

f

f0

f1

f2

f3

fn

fmax

0 Hz

P1320 P1322

P1324 P0310

P1082

MICROMASTER 420

Operating Instructions

144

6SE6400-5AA00-0BP0

Page 144