3 Functions

Issue 07/04

Using these simplifications, the thermal motor behavior can be defined using a 1st Order filter (PT1 filter). In this case, the square of the normalized motor current (measured motor current r0027 divided by the rated motor current P0305) weighted by the thermal motor time constant P0611 results in the I²t value of the motor

r0034. The I²t value represents a parameter for the temperature rise / temperature of the motor.

In addition, the output frequency (motor speed) is included in the calculation in order to take into account the cooling effect of the motor fan.

If parameter P0335 is changed to a force-ventilated motor, then the calculation is also appropriately modified.

If the I²t value of the motor (r0034) reaches the value defined in P0614 (default: 100%), alarm message A0511 is output and depending on P0610, a response is initiated, or, when the shutdown threshold is reached, a fault. The following settings are possible for P0610:

0No response, only a warning

1Warning and Imax is reduced

(this results in a lower output frequency)

2Warning and fault (F0011)

Trip threshold 1.1P0614

P0611

r0027 2

   P0305

r0021

P0310

 

 

Motor

 

 

 

 

 

 

 

 

F0011

 

 

r0034

i2t

 

 

 

 

 

 

 

 

 

temp.

 

 

I_max reduction

 

( i2 t )

 

 

t

reaction

 

 

 

 

 

 

P0610

 

 

A0511

 

 

 

 

 

 

 

 

 

 

 

P0335

P0614

Warning threshold

Fig. 3-56 Drive inverter response

The thermal motor time constant P0611 is a measure for the rate at which the motor temperature changes and must be entered depending on the motor.

NOTE

For motors with a higher weight P0344, the temperature increase characteristic is significantly slower than for small motors.

If thermal data of a third-party motor is not entered, then values are used that are based on a Siemens motor.

Thermal motor data should be taken from the appropriate motor Catalogs.

MICROMASTER 420

Operating Instructions

136

6SE6400-5AA00-0BP0