3 Functions

Issue 07/04

OFF2

The inverter pulses are immediately cancelled by the OFF2 command. This means that the motor coasts-down and it is not possible to brake in a controlled fashion.

f act

 

P1082

 

fmax

OFF2

 

r0052 Bit02

t

 

Operation

Pulse cancellation

t

Fig. 3-45

OFF2

NOTE

The OFF2 command can have one or several sources. The command sources are defined using BICO parameters P0844 (BI: 1. OFF2) and P0845 (BI: 2. OFF2).

As a result of the pre-assignment (default setting), the OFF2 command is set to the BOP. This source is still available even if another command source is defined (e.g. terminal as command source P0700 = 2 and OFF2 is selected using DIN2 P0702 = 3).

OFF3

The braking characteristics of OFF3 are identical with those of OFF1 with the exception of the autonomous OFF3 ramp-down time P1135. If the output frequency falls below parameter value P2167 and if the time in P2168 has expired, then the inverter pulses are cancelled as for the OFF1 command.

fact

 

P1082

 

 

 

 

 

fmax

OFF3

 

 

 

 

 

 

 

 

 

P2167

 

 

 

 

 

 

t

 

 

 

 

 

P2168

 

 

 

r0052 Bit02

tdown,OFF3

 

 

 

P1135

 

 

 

 

 

 

 

 

Operation

 

= P1135

f 2

 

Pulse

tdown,OFF3

 

P1082

cancellation

t

 

 

Fig. 3-46

OFF3

 

 

 

 

NOTE

OFF3 can be entered using a wide range of command sources via BICO parameters P0848 (BI: 1. OFF3) and P0849 (BI: 2. OFF3).

MICROMASTER 420

Operating Instructions