3 Functions

If the motorized potentiometer is to be used as setpoint source, then either parameter P1000 or P0719 should be modified or the BICO parameter r1050 should be connected to the main setpoint P1070 or supplementary setpoint P1075. Contrary to parameter P0719, when parameter P1000 is modified, this implicitly changes BICO parameters P1070, P1075.

Example: Setpoint via the motorized potentiometer (MOP)

a) Standard method

P1000

= 1

b) BICO method

P1070

= 1050

 

 

P1075

= 0

The MOP is configured using the following parameters and has the mode of operation as shown in Table 3-16:

Limits using the minimum frequency P1080 or maximum frequency P1082 Ramp-up/ramp-down time P1120 or P1121

Inhibits MOP reversing function P1032 Saves the MOP setpoint P1031 MOP setpoint P1040

Table 3-16 Mode of operation of the MOP

Motorized potentiometer

Function

Lower

 

Raise

 

 

 

0

 

0

Setpoint is frozen

0

 

1

Raise setpoint

 

 

 

 

1

 

0

Lower setpoint

 

 

 

 

1

 

1

Setpoint is frozen

Selecting via BOP or AOP

The following settings / operator actions should be made when selecting the motorized potentiometer using the BOP or AOP:

Table 3-17 Selecting the motorized potentiometer

Parameters / keys

BOP

 

AOP (at the BOP link)

Command

P0700

1

 

4

source

 

 

 

 

Setpoint

P1000

 

1

source

 

 

 

 

P1035

-

 

2032.13 (2032.D)

 

 

 

 

 

 

 

 

P1036

-

 

2032.14 (2032.E)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Raise MOP output frequency

 

 

 

 

 

Lower MOP output frequency

 

 

 

 

 

MICROMASTER 420

Operating Instructions

6SE6400-5AA00-0BP0

103

Page 103
Image 103
Siemens 420 manual Selecting via BOP or AOP, Parameters / keys, AOP at the BOP link