3.21.1.5Current limiting (Imax controller)

Parameter range:

P1340 – P1344

 

r0056 bit 13

Warnings

A0501

Faults

F0001

Function chart number:

FP6100

Our drive inverters have, in the V/f characteristic mode, a current limiting controller (Imax controller, refer to Fig. 3-64). This controller avoids overload conditions. This controller protects the drive inverter and the motor against continuous overload conditions by automatically reducing the drive inverter output frequency by fImax (r1343) or the drive inverter output voltage by VImax (r1344). By either reducing the output frequency or the output voltage, this reduces the load on the drive inverter and protects against continuous damage.

 

 

 

 

Imax ctrl prp gain

 

Imax ctrl int time

 

 

 

 

 

 

0.000 ... 0.499

0.000 ... 50.000 [s]

 

 

 

 

 

 

P1340.D (0.000)

 

P1346.D (0.300)

 

 

 

 

 

 

Kp

 

Tn

 

 

 

 

Motor temperatur

 

 

 

fI_max

CO:Imax ctrl Foutp

 

 

 

Inverter temperatur

 

 

 

r1343

 

 

 

 

 

 

 

 

 

 

i2t inverter

 

 

 

 

 

Motor ovl fact [%]

 

Imax controller setpoint

 

 

 

 

 

10.0 ... 400.0

[%]

 

+

 

 

 

 

P0640.D (150.0)

 

Kp

 

Tn

 

 

 

 

 

 

 

 

 

 

 

 

Motor ovl fact [%]

r0067

 

 

 

UI_max

CO:Imax ctrl Voutp

 

CO: Outp cur limit [A]

 

 

 

 

10.0 ... 400.0

[%]

 

 

 

r1344

 

P0640.D (150.0)

Current feedback

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

r0068

 

 

 

 

 

 

 

 

CO: Output current [A]

 

 

 

 

 

 

 

 

 

 

Imax ctrl prp gain

Imax ctrl int time

 

 

 

 

 

 

0.000 ... 5.499

 

0.000 ... 50.000 [s]

 

 

 

 

 

 

P1345.D (0.250)

P1346.D (0.300)

 

Fig. 3-64 Imax controller

NOTE

A reduction in the frequency only reduces the load if the load decreases at lower speeds (e.g. square-law torque-speed characteristic of the driven load).