5 MICROMASTER 420 specifications

Issue 07/04

Input voltage range

3 AC 200 V – 240 V, ± 10 %

 

 

 

 

(Unfiltered)

 

 

 

 

 

 

 

 

 

 

Order No.

6SE6420-

2UC11-

2UC12-

2UC13-

2UC15-

2UC17-

2UC21-

2UC21-

2UC22-

 

 

 

2AA1

5AA1

7AA1

5AA1

5AA1

1BA1

5BA1

2BA1

Output Rating

 

[kW]

0.12

0.25

0.37

0.55

0.75

1.1

1.5

2.2

 

[hp]

0.16

0.33

0.5

0.75

1.0

1.5

2.0

3.0

 

 

Output Power

 

[kVA]

0.4

0.7

1.0

1.3

1.7

2.4

3.2

4.6

Input Current 1)

 

[A]

1.1

1.9

2.7

3.6

4.7

6.4

8.3

11.7

 

 

 

 

 

 

 

 

 

 

 

Output Current

 

[A]

0.9

1.7

2.3

3.0

3.9

5.5

7.4

10.4

Fuse

 

[A]

10

10

10

10

10

16

16

20

 

 

 

 

 

 

 

 

 

 

 

Recommended

 

3NA

3803

3803

3803

3803

3803

3805

3805

3807

For UL specified

 

 

 

 

 

 

 

 

 

 

 

 

*

*

*

*

*

*

*

*

 

 

 

Input Cable, min.

 

[mm2]

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

 

[awg]

17

17

17

17

17

17

17

17

 

 

Input Cable, max.

 

[mm2]

2.5

2.5

2.5

2.5

2.5

6.0

6.0

6.0

 

[awg]

13

13

13

13

13

9

9

9

 

 

Output Cable, min.

 

[mm2]

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

 

[awg]

17

17

17

17

17

17

17

17

 

 

Output Cable, max.

 

[mm2]

2.5

2.5

2.5

2.5

2.5

6.0

6.0

6.0

 

[awg]

13

13

13

13

13

9

9

9

 

 

Weight

 

[kg]

1.2

1.2

1.2

1.2

1.2

2.9

2.9

3.1

 

[lbs]

2.6

2.6

2.6

2.6

2.6

6.4

6.4

6.8

 

 

 

 

 

 

 

 

 

 

 

 

Order No.

6SE6420-

2UC23-

2UC24-

2UC25-

 

 

 

 

 

 

 

 

0CA1

0CA1

5CA1

 

 

 

 

 

Output Rating

 

[kW]

3.0

4.0

5.5

 

 

 

 

 

 

[hp]

4.0

5.0

7.5

 

 

 

 

 

 

 

 

 

 

 

 

Output Power

 

[kVA]

6.0

7.7

9.6

 

 

 

 

 

Input Current 1)

 

[A]

15.6

19.7

26.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output Current

 

[A]

13.6

17.5

22.0

 

 

 

 

 

Fuse

 

[A]

25

32

35

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Recommended

 

3NA

3810

3812

3814

 

 

 

 

 

For UL specified

 

 

*

*

*

 

 

 

 

 

Input Cable, min.

 

[mm2]

2.5

2.5

4.0

 

 

 

 

 

 

[awg]

13

13

11

 

 

 

 

 

 

 

 

 

 

 

 

Input Cable, max.

 

[mm2]

10.0

10.0

10.0

 

 

 

 

 

 

[awg]

7

7

7

 

 

 

 

 

 

 

 

 

 

 

 

Output Cable, min.

 

[mm2]

1.5

2.5

4.0

 

 

 

 

 

 

[awg]

15

13

11

 

 

 

 

 

 

 

 

 

 

 

 

Output Cable, max.

 

[mm2]

10.0

10.0

10.0

 

 

 

 

 

 

[awg]

7

7

7

 

 

 

 

 

 

 

 

 

 

 

 

Weight

 

[kg]

5.2

5.5

5.5

 

 

 

 

 

 

[lbs]

11.4

12.1

12.1

 

 

 

 

 

 

 

 

 

 

 

 

1)Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line supply Vk = 1 % referred to the rated drive converter power and a rated line supply voltage of 240 V without line commutating reactor. If a line commutating reactor is used, the specified values are reduced by between 55 % and 70 %.

*UL listed fuses such as Class NON from Bussmann are required for use in America

MICROMASTER 420