Issue 07/04

3 Functions

Attribute

Attribute

 

Description

group

 

 

 

 

Access level

 

The access level is controlled using parameter P0003. In this case, only those

 

 

parameters are visible at the BOP or AOP, where the access level is less than or

 

 

equal to the value assigned in parameter P0003. On the other hand, for DriveMonitor

 

 

and STARTER, only access levels 0 and 4 are relevant. For example, parameters

 

 

with access level 4 cannot be changed if the appropriate access level has not been

 

 

set.

 

 

 

 

The following access levels are implemented in the family of MICROMASTER drive

 

 

units:

 

 

 

0

User-defined parameter list (refer to P0013)

 

 

1

Standard access to the most frequently used parameters

 

2

Extended access, e.g. to drive inverter I/O functions

 

3

Expert access only for experienced users

 

 

 

As far as the ability to visualize the parameters is concerned, the group assignment of

 

 

the individual parameters must be taken into account. Parameter P0004 is used for

 

 

the control (refer to the Grouping).

 

Grouping

 

The parameters are sub-divided into groups according to their functionality. This

 

 

increases the transparency and allows a parameter to be quickly searched for.

 

 

Furthermore, parameter P0004 can be used to control the ability to be visualized for

 

 

the BOP / AOP.

 

 

 

 

Main parameter area:

 

ALWAYS

0

all parameters

 

 

INVERTER

2

drive inverter parameters

0200 .... 0299

 

TECH_APL

5

technical applications / units

0500 .... 0599

 

COMMANDS

7

control commands, digital I/O

0700 .... 0749 and

 

 

 

 

0800 .... 0899

 

TERMINAL

8

Analog inputs/outputs

0750 .... 0799

 

SETPOINT

10

Setpoint channel and ramp-function gen.

1000 .... 1199

 

FUNC

12

Drive inverter functions

1200 .... 1299

 

CONTROL

13

Motor open-loop/closed-loop control

1300 .... 1799

 

COMM

20

Communications

2000 .... 2099

 

ALARMS

21

Faults, warnings, monitoring functions"

2100 .... 2199

 

TECH

22

Technological controller (PID controller)

2200 .... 2399

BICO

 

Description for Binector Input (BI), Binector Output (BO), Connector Input (CI),

 

 

Connector Output (CO) and Connector Output / Binector Output (CO/BO), refer to

 

 

Section 3.1.2.3

 

 

BI

Binector Input

 

 

BO

Binector Output

 

 

CI

Connector Input

 

 

CO

Connector Output

 

 

CO/BO

Connector Output / Binector Output

 

Change state

 

"P" parameters can only be changed depending on the drive state. The parameter

 

 

value is not accepted if the instantaneous state is not listed in the parameter attribute

 

 

"Change state". For instance, the commissioning (start-up) parameter P0010 with the

 

 

attribute "CT" can only be changed in quick start-up "C" or ready "T" but not in run

 

 

"U".

 

 

 

C

Quick commissioning (start-up)

 

 

U

Operation (run)

 

 

T

Ready

 

 

QC.

 

This parameter attribute identifies as to whether the parameter is included in the quick

 

 

commissioning (start-up) (P0010 = 1).

 

 

No

The parameter is not included in the quick commissioning (start-up)

 

Yes

The parameter is included in the quick commissioning (start-up)

MICROMASTER 420

Operating Instructions

6SE6400-5AA00-0BP0

41