3 Functions

Issue 07/04

Table 3-8

Example 1LA7060-4AB10

 

 

 

 

 

 

 

 

 

 

 

Delta circuit

87 Hz

Star circuit

 

 

 

configuration

characteristic

configuration

P0304

 

Rated motor voltage

230 V

400 V

400 V

 

 

 

 

 

 

P0305

 

Rated motor current

0.73 A

0.73 A

0.42 A

 

 

 

 

 

 

P0307

 

Rated motor power

120 W

207 W

120 W

P0308

 

Cos ϕ

0.75

0.75

0.75

P0310

 

Rated motor frequency

50 Hz

87 Hz

50 Hz

 

 

 

 

 

 

P0311

 

Rated motor speed

1350 RPM

2460 RPM

1350 RPM

 

 

 

 

 

 

P0314

 

Motor pole pairs

2

2

2

 

 

 

 

 

 

Contrary to the BOP, AOP operator panels or commissioning tool program DriveMonitor, the STARTER commissioning (start-up) program offers a mask- orientated quick commissioning, which is especially advantageous for users who are using MICROMASTER for the first time. On the other hand, BOP, AOP and DriveMonitor offer, in conjunction with the drive inverter, parameter-orientated quick commissioning where the user is navigated through the menu tree mentioned above.

NOTE

The MICROMASTER series of drive units is not available for 3-ph. 690 V AC.

MICROMASTER 420

Operating Instructions

68

6SE6400-5AA00-0BP0

Page 68
Image 68
Siemens 420 manual 87 Hz