3 Functions

Issue 07/04

3.6.3Analog input (ADC)

Number:

1

Parameter range:

P0750 – P0762

Function chart number:

FP2200

Features:

 

-

cycle time:

4 ms

-

resolution:

10 bits

- accuracy:

1 % referred to 10 V / 20 mA

-

electrical features:

incorrect polarity protection, short-circuit proof

Analog setpoints, actual values and control signals are read-into the drive inverter using the appropriate analog input and are converted into digital signals / values using the ADC converter.

The analog input represents a voltage input that can be additionally configured via parameter P0756.

Depending on the source, the appropriate connection must be made. Using, as an example, the internal 10 V voltage source, a connection is shown as an example in the following diagram (refer to Fig. 3-24).

Voltage input

> 4.7 k

KL1

10 V

KL2

0 V

KL3 ADC+ A

KL4 ADC

D

Fig. 3-24 Connection example for ADC voltage input

The ADC channel has several function units (filter, scaling, dead zone) (refer to Fig. 3-25).

ADC channel

 

P0756

 

P0757

P0758

P0759

P0760

r0754 P1000

 

 

 

 

P0753

P0761

 

Setpoint

 

 

 

 

 

 

 

 

 

 

 

 

KL

A

 

ADC

 

 

ADC

ADC

 

 

ADC+

 

 

 

r0755

Pxxxx

KL

 

D

type

 

 

scaling

dead

 

 

 

zone

 

 

ADC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P0756

P0761

 

 

r0752

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wire

 

 

F0080

 

 

 

 

 

 

 

breakage

 

 

 

 

 

 

 

 

 

 

sensing

 

 

r0751

 

 

 

1

1.7 V

 

 

 

 

 

r0722

Pxxxx

 

 

 

0

 

 

 

 

 

P0704

r0722.3

 

 

 

3.9 V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Function

Fig. 3-25

ADC channel

 

 

 

 

 

 

 

 

MICROMASTER 420

Operating Instructions

92

6SE6400-5AA00-0BP0

Page 92
Image 92