7 Electro-magnetic compatibility (EMC)

Issue 07/04

7.1.5Classification of EMC performance

Three General classes of EMC performance are available as detailed below:

Class 1: General Industrial

Compliance with the EMC Product Standard for Power Drive Systems EN 68100-3 for use in Second Environment (Industrial) and Restricted Distribution.

Table 7-2

Class 1 - General Industrial

 

 

 

 

EMC Phenomenon

Standard

Level

Emissions:

 

 

 

Radiated Emissions

EN 55011

Level A1

 

 

 

Conducted Emissions

EN 68100-3

Limits under consideration

 

 

 

 

Immunity:

 

 

 

Electrostatic Discharge

EN 61000-4-2

8 kV air discharge

 

 

 

Burst Interference

EN 61000-4-4

2 kV power cables, 1 kV control

 

 

 

Radio Frequency Electromagnetic Field

IEC 1000-4-3

26-1000 MHz, 10 V/m

Class 2: Filtered Industrial

This level of performance will allow the manufacturer/assembler to self-certify their apparatus for compliance with the EMC directive for the industrial environment as regards the EMC performance characteristics of the power drive system.

Performance limits are as specified in the Generic Industrial Emissions and Immunity standards EN 50081-2 and EN 50082-2.

Table 7-3

Class 2 - Filtered Industrial

 

 

 

 

EMC Phenomenon

Standard

Level

Emissions:

 

 

 

Radiated Emissions

EN 55011

Level A1

Conducted Emissions

EN 55011

Level A1

 

 

 

 

 

 

 

 

Immunity:

 

 

 

Supply Voltage Distortion

IEC 1000-2-4

 

 

 

(1993)

 

Voltage Fluctuations, Dips, Unbalance,

IEC 1000-2-1

 

Frequency Variations

 

 

Magnetic Fields

EN 61000-4-8

50 Hz, 30 A/m

Electrostatic Discharge

EN 61000-4-2

8 kV air discharge

 

 

 

Burst Interference

EN 61000-4-4

2 kV power cables, 2 kV control

 

 

 

Radio Frequency Electromagnetic

ENV 50 140

80-1000 MHz, 10 V/m, 80% AM, power

Field, amplitude modulated

 

and signal lines

Radio-frequency Electromagnetic Field,

ENV 50 204

900 MHz, 10 V/m 50% duty cycle, 200 Hz

pulse modulated

 

repetition rate

MICROMASTER 420