3 Functions

Issue 07/04

3.1.2.2Selection of command/frequency setpoint P0719

Parameter P0719 represents a combination of the functionalities of the two parameters P0700 and P1000. Here, it is possible to changeover the command source as well as also the frequency setpoint source via a parameter change. Contrary to P0700 and P1000, for parameter P0719, the subordinate (lower-level) BICO parameters are not changed. This characteristic/feature is especially used by PC tools in order to briefly retrieve the control authority for the drive without having to change the existing BICO parameterization. Parameter P0719 "Selection of command/frequency setpoint" comprises the command source (Cmd) and the frequency setpoint (setpoint).

Table 3-4

Parameter P0719

 

 

 

 

 

 

 

Parameter values

 

Significance

Command source

 

Setpoint source (frequency source)

 

 

 

0

 

Cmd = BICO parameter

 

Setpoint = BICO parameter

 

 

 

 

 

1

 

Cmd = BICO parameter

 

Setpoint = MOP setpoint

2

 

Cmd = BICO parameter

 

Setpoint = Analog setpoint

 

 

 

 

 

3

 

Cmd = BICO parameter

 

Setpoint = Fixed frequency

 

 

 

 

 

4

 

Cmd = BICO parameter

 

Setpoint = USS BOP link

5

 

Cmd = BICO parameter

 

Setpoint = USS COM link

6

 

Cmd = BICO parameter

 

Setpoint = CB COM link

 

 

 

 

 

10

 

Cmd = BOP

 

Setpoint = BICO parameter

 

 

 

 

 

11

 

Cmd = BOP

 

Setpoint = MOP setpoint

12

 

Cmd = BOP

 

Setpoint = Analog setpoint

 

 

 

 

 

..

 

..

 

..

 

 

 

 

 

..

 

..

 

..

 

 

 

 

 

64

 

Cmd = CB on COM link

 

Setpoint = USS on BOP link

66

 

Cmd = CB on COM link

 

Setpoint = USS on COM link

 

 

 

 

 

NOTE

The complete list of all of the possible settings can be taken from the parameter list (refer to the parameter list, P0719).

Contrary to parameter P0700 and P1000, subordinate BICO parameters are not changed for parameter P0719. This characteristic/feature can be used during service if the control authority must be briefly and quickly re-assigned (e.g. selecting and executing the motor data identification routine using a PC-based tool).